Unit Application Data - York HA090 Technical Manual

Split-system air-cooled condensing units
Table of Contents

Advertisement

036-21323-002-C-0206
TABLE 1: UNIT APPLICATION DATA
Voltage Variation (208/230-3-60) - Volts
Ambient Air on Outdoor Coil (Cooling Cycle) - F
Ambient Air on I ndoor Coil (Cooling Cycle) - F
TABLE 2: ARI RATINGS - COOLING AND SOUND
Model
Outdoor
I ndoor Unit
Unit
HB180
KB180
HB240
KB240
1. Ratings are in accordance with ARI standard 340/ 360.
2. Ratings are in accordance with ARI standard 370.
TABLE 3: ELECTRICAL DATA COMPRESSORS
Model
Number
HB180
HB180
HB180
HB240
HB240
HB240
TABLE 4: ELECTRICAL DATA FAN MOTORS
Model
Number
HB180
HB180
HB180
HB240
HB240
HB240
TABLE 5: ELECTRICAL DATA, OUTDOOR MCA & MAX. FUSE SIZE
Model
Number
HB180
HB180
HB180
HB240
HB240
HB240
1. Maximum f use or maximum circuit breaker (HACR type per NEC).
Unitary Products Group
http://www.rezine.net
Application Limitations
Voltage Variation (460-3-60) - Volts
Voltage Variation (575-3-60) - Volts
Cooling Capacity
MBH
EER
180
9.7
240
9.7
Power
Supply
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
Power
Supply
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
Power
Supply
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
Page 79
Cond. Unit
1
2
Sound
I PL V
dB
10.4
89.0
10.4
90.0
Compressors
System 1
RLA
LRA
25.6
190.0
12.8
95.0
10.2
75
42.0
239.0
19.2
125.0
13.8
80
Condenser Fans
Min. Circuit
Ampacity
65.1
32.5
26.4
106.1
49.0
35.5
Minimum
Maximum
187
253
414
506
540
630
45
115
68
86
Rated Airf low
Rated ESP
CFM
I WG
6000
0.35
8000
0.40
System 2
RLA
LRA
25.6
190.0
12.8
95.0
10.2
75
42.0
239.0
19.2
125.0
13.8
80
FLA
Qty.
ea.
2
3.7
2
1.85
2
1.7
2
5.8
2
2.9
2
2.2
Max.
Fuse
1
Size
90
45
35
125
60
45
7

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents