TECHNICAL GUIDE
SPLIT-SYSTEM
AIR COOLED
CONDENSING UNITS
MODELS: HA120
10 NOMINAL TONS
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
http://www.rezine.net
DESCRIPTION
®
These outdoor condensing units are completely assembled, piped and
wired at the factory to provide one-piece shipment and rigging. Each
unit is pressurized with a holding charge of refrigerant-22 for storage
and/or shipping.
The compact design, clean styling, and quiet operation make these
condensing units suitable for almost any outdoor location. On rooftops
. . . because they weigh much less than a single package unit of simi-
lar capacity and are much easier to rig and support. At ground level. . .
because their ample sub-cooling capacity allows them to be located 18
meters (60 feet) below the evaporator coil.
All sheet metal parts are constructed of commercial grade (G90) gal-
vanized steel. Before painting, each part is thoroughly cleaned to
remove any grease or dirt from its surfaces. The external parts are
then coated with a powder paint to assure a quality finish for many
years. This coating system has passed the 100 hour, salt spray test
per ASTM Standard B117.
All models include a 1-year limited warranty on the complete unit. The
compressor carries an additional 4-year warranty.
A matching line of Evaporator Blower units is also offered to meet your
precise capacity and air handling requirements.
FEATURES
Condenser coil constructed of rifled copper tubes and louvered
O
aluminum fins for durability and long lasting efficient operation.
O
Permanently attached base rails with fork lift slots and lifting
holes. This design allows for 3-way fork lift access and overhead
O
rigging.
Both high and low pressure controls.
Solid state motor protection to prevent the compressor from oper-
ating at an unsafe condition.
Ball bearing condenser fan motors with 1/2 inch shafts.
Color-coded power and control wiring for easier service and trou-
bleshooting.
Anti-short cycle timer to protect the compressor.
A lockout circuit to prevent the unit from cycling on safety control.
A 24-volt temperature control circuit.
Standard unit low ambient operation to (35°F).
A filter-drier (shipped in the unit's compressor compartment for
field installation near the evaporator coil).
Service valves with a back-seating access port for pressure test-
ing the system. Copper stub-outs are factory mounted on the suc-
tion and liquid service valves to simplify the field piping
connections.
Exterior access to service pressure port connections.
Packaging suitable for outdoor storage.
An optional Phenolic coating is available where the condenser
coils are fully dipped in a phenolic coating process to provide
longer life in corrosive conditions.