Trim Piping; System Piping - UTICA BOILERS UBSSC-050 Installation, Operation & Maintanance Manual

Wall mounted gas boiler
Table of Contents

Advertisement

WARNING
!
Burn and scald hazard. Safety relief valve could
discharge steam or hot water during operation.
Install discharge piping per these instructions.
FIGURE 5-2 Safety Relief Valve Discharge Piping
Check Local Codes
For Maximum
Distance To Floor
FIGURE 5-3 Temperature Pressure Gauge and
Drain Valve Installations
Temperature Pressure
Gauge shown at
System Supply
Connection
5 - HYDRONIC PIPING
Safety Relief Valve
Gas Supply
Drain Valve shown
at System Return
Connection to Boiler
fi gure 5-2.
Use ¾" or larger pipe.
Use pipe suitable for temperatures of 375°F (191°C)
or greater.
Individual boiler discharge piping shall be independent
of other discharge piping.
Size and arrange discharge piping to avoid reducing
safety relief valve relieving capacity below minimum
relief valve capacity stated on rating plate.
Run pipe as short and straight as possible to location
protecting user from scalding and properly drain
piping.
Install union, if used, close to safety relief valve outlet.
Install elbow(s), if used, close to safety relief valve
outlet and downstream of union (if used).
Terminate pipe with plain end (not threaded).

5.4 Trim Piping

Temperature - Pressure Gauge. Install temperature
pressure gauge using nipple, tee and bushing provided
with boiler. See fi gure 5-3.
Drain Valve. Install drain valve using nipple, tee and
bushing provided with boiler. See fi gure 5-3.

5.5 System Piping

Systems with automatic fi ll valves require back fl ow
prevention device.
Single boiler system. See fi gures 5-4, 5-5, 5-6, 5-7 for
general guidance. Additional considerations:
Control system designed for single central heating
pump. Installer responsible for integration of
multiple central heating pumps.
Control system allows domestic hot water
prioritization. Function could be lost if central
heating pump not directly connected to control
system.
Multiple boiler system. See fi gure 5-8 for general
guidance. Additional considerations:
Control system requires equivalent water
temperatures entering each boiler to properly
sequence and adjust system supply temperature.
Install multi boiler sensor kit. See "Parts, Kits &
Optional Accessories" manual for part number.
12