Outdoor reset boost function increases CH set point by
increment ('Temp') if CH demand continues beyond pre-set
time limit ('Time').
CH set point will continue to increase until set point reaches
195°F / 91°C
0
1 0 ° F
2 0 m i n ▼
Allowable Temperature Increment: 0..36 °F (0..20 °C)
Default Temperature increment:
Allowable Time Delay: 1..120 minutes
Default Time Delay:
Maximum boiler power in CH mode limited by adjusting
'Maximum Power CH' setting. Boiler will not exceed this
value while operating in CH Mode.
C H
Allowable Range: 1..100%
1 0 0 %
Default Setting:
Two DHW modes are available
• DHW Mode = 2 'DHW Store with Thermostat'
M O D E : 1
w i t h
Note:
69
Explanation
20 minutes
100%
DHW Mode = 0 'No DHW
DHW Mode is disabled
The DHW thermostat input is ignored and the DHW
pump is not used.
Boiler reacts to DHW demand when DHW thermostat
input closes.
Boiler modulates to meet DHW demand similar to CH
Mode except DHW set point is used. DHW set point set
in Settings' submenu found in 'User Menu'.
Simultaneous CH & DHW demands handled using DHW
Priority Timing. See 'DHW Maximum Priority Time'
setting below.
Outdoor reset function disabled while operating in DHW
Mode.
Typical when using a DHW indirect storage tank.
After DHW demand satisfi ed, boiler enters post purge
mode and DHW pump continues to run for 15 seconds.
0 °F (10 °C)