UTICA BOILERS UBSSC-050 Installation, Operation & Maintanance Manual page 62

Wall mounted gas boiler
Table of Contents

Advertisement

User Interface Display
S E T T I N G S
C e n t r a l
H e a t i n g
S e t p o i n t
Setting Range: 104° F to 195° F (40° C to 91° C)
Default Value: 140° F (60° C)
S E T T I N G S
D H W
S e t p o i n t
Setting Range: 104° F to 195° F (40° C to 91° C)
Default Value:
180° F (82° C)
S E T T I N G S
C h a n g e
T e m p e r a t u r e
F a h r e n h e i t
APPENDIX A - CONTROL MODULE
Adjust CH set point to hydronic system design while in
Operating in CH Mode = 0 (CH with Thermostat) or 3
(Permanent Demand).
In CH Mode = 1 (CH with Thermostat and Outdoor Reset) or 2
(CH with Full Outdoor Reset). Display will change to 'OD Reset
Setpoint' and cannot be changed. Controller calculates set point
based on outdoor temperature.
Note: For explanation of available CH heating modes, refer to
° F
'CH Mode' section located in 'CH Settings' submenu.
DHW set point determines supply water temperature set point
while operating in DHW mode.
° F
User interface temperature unit of measure is selected using
'Change Temperature Units' screen.
Fahrenheit and Celsius available.
U n i t s
° F
62