Weil-McLain Gold CGi 2 Series Manual page 6

Gold cgi gas-fired water boilers series 2
Hide thumbs Also See for Gold CGi 2 Series:
Table of Contents

Advertisement

CGi
GOLD
GAS-FIRED WATER BOILER — SERIES 2 —
1a
Prepare boiler location — codes & checklist
6
Installations must follow these codes:
Local, state, provincial, and national codes, laws, regulations and ordinances.
National Fuel Gas Code, ANSI Z223.1 –– latest edition.
Standard for Controls and Safety Devices for Automatically Fired Boilers,
ANSI/ASME CSD-1, when required.
National Electrical Code.
For Canada only: B149.1 or B149.2 Installation Code, CSA C22.1 Canadian
Electrical Code Part 1 and any local codes.
The CGi boiler gas manifold and controls met safe lighting and
other performance criteria when boiler underwent tests specified
in ANSI Z21.13 –– latest edition.
For the Commonwealth of Massachusetts, read and follow the
special instructions located on page 15 of this manual.
Before locating the boiler, check the
following:
Check for nearby connection to:
System water piping
Venting connections
Gas supply piping
Electrical power
Check area around boiler.
other flammable liquids, or other contaminants
Failure to keep boiler area clear and free of
rials, gasoline and other flammable liquids and vapors
result in severe personal injury, death or substantial property
damage.
Boiler must be installed so that gas control system components are protected
from dripping or spraying water or rain during operation or service.
If new boiler will replace existing boiler, check for and correct system problems,
such as:
1. System leaks causing oxygen corrosion or section cracks from hard water
deposits.
2. Incorrectly-sized expansion tank.
3. Lack of antifreeze in boiler water causing system and boiler to freeze and
leak.
Boiler Manual
Remove any combustible materials, gasoline and
.
combustible mate-
can
Part Number 550-110-710/1211

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents