Daikin RQYQ140-180PY1 Service Manual page 94

R-410a heat pump 50hz and r-410a heat recovery 50hz
Table of Contents

Advertisement

Field Setting from Outdoor Unit
Set cool/heat at all outdoor unit systems simultaneously for each outdoor unit external control adaptor
by using the central remote controller.
85
Install the outdoor unit external control adaptor (optional accessory) onto the outdoor-
outdoor, indoor-outdoor, or indoor-indoor transmission line.
Use "setting mode 1" and set all outdoor units to SLAVE.
Set the outdoor unit external control adaptor SS1 to BOTH (factory set) or C/H and set SS2 to ON.
Use "setting mode 2" and set DS1 and DS2 on the outdoor unit external control adaptors
and the unified heat/cool address on the outdoor unit main PCB to the same address. (The
factory set addresses are all "0".)
SiBE341001
Test Operation