Normal Operation - Daikin RQYQ140-180PY1 Service Manual

R-410a heat pump 50hz and r-410a heat recovery 50hz
Table of Contents

Advertisement

Detailed Control Functions
2.5

Normal Operation

2.5.1 List of Functions in Normal Operation
<Outdoor Unit>
Part Name
Compressor
Outdoor unit fan
Electronic expansion valve
(Main)
Electronic expansion valve
(Subcooling)
Electronic expansion valve
(Refrigerant charge)
Solenoid valve (Refrigerant
regulator hot gas)
Solenoid valve (Refrigerant
regulator liquid pipe)
Solenoid valve (Refrigerant
regulator gas vent pipe)
Solenoid valve (Hot gas)
Solenoid valve (Circuit of oil
return)
Four way valve (Heat
exchanger switch)
Four way valve (Dual
pressure gas pipe)
Four way valve (Mixing unit)
Solenoid valve (Mixing unit
inlet)
<Indoor Unit>
Part Name
Indoor unit fan
Electronic expansion valve
(Main)
<BS Unit>
Part Name
Electronic expansion valve
(EVSC)
Electronic expansion valve
(EVHS)
Electronic expansion valve
(EVLS)
Electronic expansion valve
(EVH)
Electronic expansion valve
(EVL)
39
Electric
Normal Cooling
Symbol
PI control, High pressure
protection, Low pressure
M1C
protection, Td protection,
INV protection
M1F
Cooling fan control
Y1E
480 pls
Y3E
PI control
41 pls for refrigerant
Y2E
discharge
ON for refrigerant
Y1S
discharge
ON for refrigerant
Y2S
recovery
ON for refrigerant
Y3S
recovery
Y4S
OFF
Y5S
ON
Y6S
OFF
Y7S
ON
Y8S
OFF
Y9S
OFF
Normal cooling
Electric
Thermostat
Thermostat
Symbol
ON unit
OFF unit
Remote
Remote
M1F
controller
controller
setting
Normal
Y1E
opening
Electric
Normal cooling
Symbol
Y1E
Y2E
480 pls ( fully opened )
Y3E
480 pls ( fully opened )
Y4E
760 pls ( fully opened )
Y5E
760 pls ( fully opened )
Normal Heating
PI control, High pressure
protection, Low pressure
protection, Td protection,
INV protection
• Outdoor unit heat
exchanger: Condenser /
Cooling fan control
• Outdoor unit heat
exchanger: Evaporator /
Fan step 7 or 8
• Outdoor unit heat
exchanger: Condenser /
Liquid pressure control
• Outdoor unit heat
exchanger: Evaporator /
PI control
PI control
41 pls for refrigerant
discharge
ON for refrigerant
discharge
ON for refrigerant
recovery
ON for refrigerant
recovery
OFF
ON
• Outdoor unit heat
exchanger: Condenser /
OFF
• Outdoor unit heat
exchanger: Evaporator /
ON
OFF
OFF
OFF
Stopping
Thermostat
unit
OFF
controller
setting
0 pls
0 pls
0 pls
SiBE341001
Normal Simultaneous
Cooling / Heating
PI control, High pressure
protection, Low pressure
protection, Td protection,
INV protection
• Outdoor unit heat
exchanger: Condenser /
Cooling fan control
• Outdoor unit heat
exchanger: Evaporator /
Fan step 7 or 8
• Outdoor unit heat
exchanger: Condenser /
Liquid pressure control
• Outdoor unit heat
exchanger: Evaporator /
PI control
PI control
41 pls for refrigerant
discharge
ON for refrigerant
discharge
ON for refrigerant
recovery
ON for refrigerant
recovery
OFF
ON
• Outdoor unit heat
exchanger: Condenser /
OFF
• Outdoor unit heat
exchanger: Evaporator /
ON
OFF
OFF
OFF
Normal heating
Thermostat
ON unit
OFF unit
Remote
LL
setting
Normal
192 pls
opening
Normal heating
0 pls
480 pls ( fully opened )
0 pls
760 pls ( fully opened )
0 pls
Stopping
unit
OFF
192 pls
Function