CHECK 4
Power Transistor Check
Perform the following procedures prior to check.
(1) Power Off.
(2) Remove all the wiring connected to the PCB where power transistors are mounted on.
[Preparation]
· Tester
[Point of Measurement and Judgement Criteria]
· Measure the resistance value using a tester at each point of measurement below, 10 minutes later after power OFF.
To use analog tester:
Measurement in the resistance value mode in the range of
multiplying 1kΩ.
Point of Measurement
No.
+
1
P2
U
2
P2
V
3
P2
W
4
U
P2
5
V
P2
6
W
P2
7
N3
U
8
N3
V
9
N3
W
10
U
N3
11
V
N3
12
W
N3
[PCB and Circuit Diagram]
Troubleshooting
Judgement Criteria
Remarks
2 ~ 15kΩ
Due to condenser charge
15kΩ and
and so on, resistance
above
measurement may require
(including )
some time.
2 ~ 15kΩ
Troubleshooting by Remote Controller
∗ Preparing a tester in the analog system is recommended.
A tester in the digital system with diode check function will
be usable.
To use digital tester:
Measurement is executed in the diode check mode. (
Point of Measurement
No.
Judgement Criteria
+
1
P2
U
1.2V and over
2
P2
V
3
P2
W
4
U
P2
5
V
P2
6
W
P2
0.3 ~ 0.7V
7
N3
U
8
N3
V
9
N3
W
10
U
N3
11
V
N3
1.2V and over
12
W
N3
)
Remarks
Due to condenser charge
and so on, resistance
measurement may require
some time.
Due to condenser charge
and so on, resistance
measurement may require
some time.
192