E3 " Outdoor Unit: Actuation Of High Pressure Switch - Daikin RQYQ140-180PY1 Service Manual

R-410a heat pump 50hz and r-410a heat recovery 50hz
Table of Contents

Advertisement

SiBE341001
E3
"
" Outdoor Unit: Actuation of High Pressure Switch
2.8
E3
Remote
Controller
Display
Applicable
RQYQ-PY1
Models
RQEQ-PY1
Method of
Use the protection device circuit to detect continuity at the high pressure switch.
Malfunction
Detection
Malfunction
Abnormality is detected when the contact of the high pressure protection switch opens.
(Reference) Operating pressure of high pressure switch
Decision
Operating pressure: 4.0MPa
Conditions
Reset pressure:
Supposed
Causes
Troubleshooting
3.0MPa
Actuation of outdoor unit high pressure switch
Defect of high pressure switch
Defect of outdoor unit main PCB (A1P)
Instantaneous power failure
Faulty high pressure sensor
Troubleshooting by Remote Controller