2.5.2 Compressor PI Control

Carries out the compressor capacity PI control to maintain Te at constant during cooling operation and Tc at constant
during heating operation to ensure stable unit performance.
[Cooling operation]
Controls compressor capacity to adjust Te to achieve target value (TeS).
Te set value (Make this setting while in Setting mode 2.)
Te setting
L
M (Normal)
(factory setting)
3ºC
6ºC
Te : Low pressure equivalent saturation temperature (°C)
TeS : Target temperature of Te (Varies depending on Te setting, operating frequency, etc.)
* On multi-outdoor-unit systems, this control is made according to values of the first-priority unit, which is detected with
the pressure sensor.
[Heating operation]
Controls compressor capacity to adjust Tc to achieve target value (TcS).
Tc set value (Make this setting while in Setting mode 2.)
Tc setting
L
M (Normal)
(factory setting)
43ºC
46ºC
Tc : High pressure equivalent saturation temperature (°C)
TcS : Target temperature of Tc (Varies depending on Tc setting, operating frequency, etc.)
* On multi-outdoor-unit systems, this control is made according to values of the first-priority unit, which is detected with
the pressure sensor.
Function
H
7ºC
8ºC
9ºC
H
47ºC
Detailed Control Functions
10ºC
11ºC
40