L5 " Outdoor Unit: Momentary Overcurrent Of Inverter Compressor - Daikin RQYQ140-180PY1 Service Manual

R-410a heat pump 50hz and r-410a heat recovery 50hz
Table of Contents

Advertisement

SiBE341001
L5
2.23 "
" Outdoor Unit: Momentary Overcurrent of Inverter
Compressor
L5
Remote
Controller
Display
Applicable
RQYQ-PY1
RQEQ-PY1
Models
Method of
Malfunction is detected from the current flowing in the power transistor.
Malfunction
Detection
Malfunction
When an excessive current (59.1A) flows in the power transistor.
(Instantaneous overcurrent also causes activation.)
Decision
Conditions
Supposed
Causes
Troubleshooting
Defect of compressor coil (disconnected, defective insulation)
Compressor start-up malfunction (mechanical lock)
Defect of inverter PCB
Troubleshooting by Remote Controller