Typical Condensate Drain, Vertical Installation; Typical Combustion Pipe Drain Tee - Johnson Controls TP9C C Installation Manual

Residential gas furnace with ecm motor
Hide thumbs Also See for TP9C C:
Table of Contents

Advertisement

681292-UIM-A-0211
FIGURE 27: Typical Condensate drain, vertical installation
The condensate will flow to the drain better if an open stand pipe is
installed in the drain line. See Figure 27.
If evaporator coil or humidifier drains are combined with the furnace
drain, then the open stand pipe could be raised higher, above the 5"
minimum.
NOTICE
A loop has been added to the pressure switch vacuum hose. How-
ever, ensure that all pressure switch hoses are routed such that
they prevent any condensate from entering the pressure switch.
It is possible for condensation to form inside the combustion air
(intake) pipe in the summer months if significant length of combus-
tion air pipe passes through conditioned space. This problem can
be averted by the addition of a simple drain tee, or a drain tee with a
drain on the combustion air pipe as close to the furnace as possi-
ble, as shown in Figure 28. This is true for all long horizontal vent-
ing in any furnace configuration. This will prevent the condensate
from entering the furnace.
22
Open Stand Pipe
(Anti-s iphon air vent)
5" Min.
Tee
To Open Or
Vented Drain
FIGURE 28: Typical Combustion Pipe Drain Tee
CONDENSATE DRAIN TERMINATION
A condensate sump pump MUST be used if required by local codes, or
if no indoor floor drain is available. The condensate sump pump must
be approved for use with acidic condensate.
DO NOT terminate the condensate drain in a chimney, or where the
drain line may freeze. If the drain line will be exposed to tempera-
tures below freezing, adequate measures must be taken to prevent
the drain line from freezing. Failure to provide proper protection
from freezing can result in improper operation or damage to the
equipment and possible property damage. When exposed to tem-
peratures below freezing, use of a 3 to 6 watt per foot at 115 VAC,
40°F (4.4°C) self-regulating, shielded and waterproof heat tape is
recommended on the drain line outside the furnace.
DO NOT trap the drain line at any other location than at the conden-
sate drain trap supplied with the furnace.
Liquid anti-freeze will cause damage to internal plastic parts of this
furnace. DO NOT attempt to winterize the furnace using liquid
anti-freeze.
Exhaust Pipe
Combustion Air Pipe
Tee with Drain Trap
Trap
Connect to Drain
Johnson Controls Unitary Products

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tp9c*cYp9c*cCp9c*cLp9c*cYp9c cCp9c c ... Show all

Table of Contents