Thermostat Chart - Two Stage Heat Pump - Variable Speed Modulating Furnace - Johnson Controls TP9C C Installation Manual

Residential gas furnace with ecm motor
Hide thumbs Also See for TP9C C:
Table of Contents

Advertisement

681292-UIM-A-0211
THERMOSTAT
*PP32U70124
C
24 – Volt Common
Y
First Stage Compressor
R
24 – Volt Hot
(Heat XFMR)
G
Fan
E
Emergency Heat
RC
24 – Volt Hot
(Cool XFMR)
O/B
Reversing Valve
L
Malfunction Light
Y2
Second
Stage Compressor
AUX
Auxiliary Heat
3
Thermostat Installer Setup
0170-System Type-
must be set to 12
3 Heat/2 Heat Pump
Thermostat Installer Setup
0190-Changeover Valve-
must be set to 0
O/B terminal
Energized in Cooling
Thermostat Installer Setup
0200-Backup Heat Source-
must be set to 1
Heat Pump Backup Heat
Source is Fossil Fuel
Thermostat Installer Setup
0210-External Fossil Fuel
Kit- must be set to 1
Heat Pump Control
is Controlling Heat Pump
Backup Heat
FIGURE 26: Thermostat Chart - Two Stage Heat Pump – Variable Speed Modulating Furnace
20
THERMOSTAT
*DN22H00124
*DP22U70124
C
24 – Volt Common
Y1
First Stage Compressor
R
24 – Volt Hot
G
Fan
W2
Second Stage Aux. Heat
O
Reversing Valve
Energized in Cool
L
Malfunction Light
Y2
Second
Stage Compressor
E/W1
First Stage Aux. Heat
External Humidistat
(Optional)
Open on Humidity Rise
Step 1 of Thermostat
Installer/Configuration
Menu must be set to "HP2"
Selection of GAS/ELEC
switch on thermostat
not necessary
ID MODELS
TP9C
YP9C
CP9C
LP9C
MODULATING
FURNACE
MODULATING
2
FURNACE CONTROL
C
24 – Volt Common
Y1
Single
Stage Compressor
R
24 – Volt Hot
G
Fan
W
Modulating Heat
Y/Y2
Second or Full
Stage Compressor
O
Reversing Valve
Energized in Cool
LO COMP
Single Stage
Compressor (OUT)
HI COMP
Second Stage
Compressor (OUT)
DHUM
Dehumidification-
Open on Humidity Rise
Move HUMIDISTAT
jumper to "YES"
if humidistat is to be used.
Part Numbers:
2
SAP =
Legacy
OD MODELS
YZE
YZH
H*5
H*8
TWO STAGE
HEAT PUMP
YORKGUARD VI
CONTROL
C
24 – Volt Common
Y1
Single
Stage Compressor
R
24 – Volt Hot
W1 OUT
First Stage Heat
W2 OUT
Second Stage Heat
Y2 OUT
Second
Stage Compressor
O
Reversing Valve
Energized in Cool
X/L
Malfunction Light
Y2
Second
Stage Compressor
W
Auxiliary Heat
BSG
Bonnet Sensor
Bonnet Sensor
(Optional)
BS
Bonnet Sensor
Change FFuel jumper
on the heat pump control
to "ON"
Change Hot Heat Pump
jumper on the heat
pump control to "ON" if
Hot Heat Pump
Operation is desired.
Part Numbers:
SAP =
126768 = 031-09137
18395 = 031-01996
340512 = 031-09178
Johnson Controls Unitary Products
1
1
Legacy

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tp9c*cYp9c*cCp9c*cLp9c*cYp9c cCp9c c ... Show all

Table of Contents