Condensate 
(indoor models only) 
Condensate forma on can occur in high efficiency 
direct vent appliances.  Without proper drainage 
condensate will damage the heat exchanger.   
To prevent condensate damage follow these 
instruc ons. 
DO NOT 
Do not allow condensate to enter the water 
heater. 
Do not connect the condensate drain pipe directly 
to the rain sewer. 
Do not connect the condensate drain line with an 
air condi oning evaporator coil drain. 
MUST DO 
Use only vent that is approved and iden fied as 
acceptable for your par cular model. 
For ver cal termina ons, install a condensate drain 
and trap as close as possible to the appliance. 
Slope the ven ng toward the appliance according 
to the vent manufacturers installa on instruc ons. 
All condensate must drain and be disposed of 
according to local codes. 
Use only PVC or CPVC pipe for the condensate 
drain line.   
The condensate drain pipe (along its en re length) 
must be at least the same diameter as the drain 
line, (5/8 inch NPT). 
The end of the condensate drain pipe should be 
open to the atmosphere.  The end should not be 
under water or other substances. 
To minimize freezing of the condensate, run the 
condensate drain line through an interior wall or 
between insula on and an interior wall. 
The condensate collector should be used for all 
hydronic hea ng applica ons. 
 
INFORMATION 
A condensate trap is available, P/N 222053.   
Regions of cold climate will create more 
condensate in the vent system.  The condensate 
collector should be used in cold climates. 
The condensate drain pipe should be as short as 
possible and have a downward pitch. 
Checklist for Ven ng and 
Condensate (indoor models only) 
□ 
Verify proper clearances around the vents and air 
intakes. 
□ 
Ensure you have used the correct ven ng 
products for the model installed and that you 
have completely followed the ven ng 
manufacturer's installa on instruc ons and these 
installa on instruc ons. 
□ 
Verify that the vent pipe has a downward slope or 
grade to the outside of 1/4 inch per foot (1.2°)  
OR if the vent pipe is sloped toward the water 
heater (as some local codes require), that a 
condensate collector is installed to allow 
condensa on to drain away from the water 
heater to a proper drain source. 
□ 
Verify that condensate will not be allowed to 
drain back into the water heater. 
□ 
Verify that the vent system does not exceed the 
maximum length for the number of elbows used.  
Value Series Manual 
15 