Advertisement

Installing a Remote Emergency Power−Off Control
NOTE Remote EPO switch rating is 24 Vdc, 1A minimum if supplied by user.
NOTE This switch must be a dedicated switch not tied into any other circuits.
4. If you are installing multiple Remote EPO stations, wire additional stations in
5. If required, install ½-in. conduit and wiring from the Remote EPO station to trip
6. Secure the UPS by reversing all steps taken to prepare it for Remote EPO
7−2
EATON Powerware
Remote
EPO
Switch
Twisted Wires (2)

Figure 7-2. Remote EPO

parallel with the first Remote EPO.
circuitry of upstream protective devices. A normally−open contact is provided, as
shown in Figure 7-2. Remote EPO switch wiring must be in accordance with UL
Class II requirements.
installation.
9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com
®