Installing A Remote Emergency Power−Off Control; Figure 7-1. Remote Epo Control - Eaton Powerware 9315 Installation Manual

300–500 kva гзы
Hide thumbs Also See for Powerware 9315:
Table of Contents

Advertisement

Chapter 7
The Remote EPO control arrives as shown in Figure 7-1. For enclosure dimensions, side
views, and knockout patterns, see Drawing 164201118−9 on page A−36.
To UPS
To install a Remote EPO control:
Table 7-1. Remote EPO Wire Terminations
From Remote EPO Station(s)
9315 UPS (300–500 kVA) Installation Manual S 164201118 Rev H www.powerware.com
EATON Powerware
®
Installing a Remote Emergency Power−Off Control

Figure 7-1. Remote EPO Control

1. Securely mount the Remote EPO station. Recommended locations include
operator's consoles or exit doors.
2. Install wiring from the Remote EPO station using ½-in. conduit through the cable
entry panels in either the top or bottom of the UPS.
3. Connect the Remote EPO wiring as shown in Table 7-1 and Figure 7-2:
To Communication Panel in UPS
TB1−4
TB1−5
UNINTERRUPTIBLE POWER SYSTEM
To Other Equipment
TB2−1
TB2−2
EMERGENCY OFF
Remarks
Twisted wires (2) 14−18 gauge
7−1

Advertisement

Table of Contents
loading

Table of Contents