Concealed Duct High Static Pressure
5

FAN CHARACTERISTICS

Current value as a criterion, adjust the air volume value to become within the range of the chart below.
<RAV-SM2242 Type>
Standard air volume: 3600m³/h
8
7.5
7
6.5
6
5.5
5
4.5
4
300
250
200
150
100
50
5
2800
3000
3400
2880
3200
3600
Lower limit of air volume
Air volume (m³/h)
Installation Manual
High static pressure tap (50Hz)
Medium static pressure tap (50Hz)
Low static pressure tap (50Hz)
High static pressure tap (50Hz)
Medium static pressure tap (50Hz)
Low static pressure tap (50Hz)
3800
4200
4400
4000
4320
Upper limit of air volume
– 15 –
Concealed Duct High Static Pressure
<RAV-SM2802 Type>
Standard air volume: 4200m³/h
8.5
8
7.5
7
6.5
6
5.5
5
4.5
4
350
300
250
200
150
100
50
5
3200
3400
3800
4200
3360
3600
4000
Lower limit of air volume
Air volume (m³/h)
REQUIREMENT
Add a air volume damper to the air supply duct, and adjust the air volume in the range from 80% to 120% of the standard
air volume.
Installation Manual
High static pressure tap (50Hz)
Medium static pressure tap (50Hz)
Low static pressure tap (50Hz)
High static pressure tap (50Hz)
Medium static pressure tap (50Hz)
Low static pressure tap (50Hz)
4600
5000 5200
4400
4800
5040
Upper limit of air volume
– 16 –