Toshiba RAV-SM2242DT-E Installation Manual
Toshiba RAV-SM2242DT-E Installation Manual

Toshiba RAV-SM2242DT-E Installation Manual

Concealed duct high static pressure type
Hide thumbs Also See for RAV-SM2242DT-E:

Advertisement

AIR CONDITIONER (SPLIT TYPE)

Installation Manual

Indoor Unit

Model name:
Concealed Duct High Static Pressure Type
RAV-SM2242DT-E
RAV-SM2802DT-E
Installation Manual
Air conditioner
(Split type)
Manuel d'installation
Climatiseur
(Type split)
Installationsanleitung
Klimagerät
(Split-typ)
Manuale di installazione
Condizionatore d'aria
(Tipo split)
Manual de instalación
Aire acondicionado
(Tipo split)
English
1
Français
41
Deutsch
81
Italiano
121
Español
161

Advertisement

Table of Contents
loading

Summary of Contents for Toshiba RAV-SM2242DT-E

  • Page 1: Installation Manual

    AIR CONDITIONER (SPLIT TYPE) Installation Manual Indoor Unit Model name: Concealed Duct High Static Pressure Type RAV-SM2242DT-E RAV-SM2802DT-E Installation Manual Air conditioner (Split type) Manuel d’installation Climatiseur (Type split) Installationsanleitung Klimagerät (Split-typ) Manuale di installazione Condizionatore d’aria (Tipo split) Manual de instalación...
  • Page 2: Table Of Contents

    Concealed Duct High Static Pressure Original instruction This Air Conditioner uses R410A an environmentally friendly refrigerant. Contents 1 PRECAUTIONS FOR SAFETY..........5 2 ACCESSORY PARTS.
  • Page 3 • The qualified installer is a person who installs, maintains, relocates and removes the air conditioners made by Toshiba Carrier Corporation. He or she has been trained to install, maintain, relocate and remove the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such operations by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to these operations.
  • Page 4 Concealed Duct High Static Pressure Definition of Protective Gear When the air conditioner is to be transported, installed, maintained, repaired or removed, wear protective gloves and ‘safety’ work clothing. In addition to such normal protective gear, wear the protective gear described below when undertaking the special work detailed in the table below.
  • Page 5: Warning Indications On The Air Conditioner Unit

    Concealed Duct High Static Pressure „ Warning Indications on the Air Conditioner Unit Warning indication WARNING ELECTRICAL SHOCK HAZARD Disconnect all remote electric power supplies before servicing. WARNING Moving parts. Do not operate unit with grille removed. Stop the unit before the servicing. CAUTION High temperature parts.
  • Page 6: Precautions For Safety

    Concealed Duct High Static Pressure PRECAUTIONS FOR SAFETY General • Before starting to install the air conditioner, read carefully through the Installation Manual, and follow its instructions to install the air conditioner. • Only a qualified installer(*1) or qualified service person(*1) is allowed to install the air conditioner. If the air conditioner is installed by an unqualified individual, a fire, electric shocks, injury, water leakage, noise and/or vibration may result.
  • Page 7 Concealed Duct High Static Pressure Refrigerant piping • Install the refrigerant pipe securely during the installation work before operating the air conditioner. If the compressor is operated with the valve open and without refrigerant pipe, the compressor sucks air and the refrigeration cycles is over pressurized, which may cause a injury.
  • Page 8 Concealed Duct High Static Pressure New Refrigerant Air Conditioner Installation • THIS AIR CONDITIONER ADOPTS THE NEW HFC REFRIGERANT (R410A) WHICH DOES NOT DESTROY OZONE LAYER. • The characteristics of R410A refrigerant are; easy to absorb water, oxidizing membrane or oil, and its pressure is approx. 1.6 times higher than that of refrigerant R22.
  • Page 9: Accessory Parts

    Concealed Duct High Static Pressure ACCESSORY PARTS Part name Q’ty Installation Manual Owner’s Manual Heat insulator Joint (Ø22.2 – Ø28.6 mm) Shape (Be sure to hand over to customers) This manual (For other languages that do not appear in this Installation Manual, please refer to the enclosed CD-R.) (Be sure to hand over to customers) For heat insulation of Gas pipe connecting section...
  • Page 10: Selection Of Installation Place

    Concealed Duct High Static Pressure SELECTION OF INSTALLATION PLACE Upon approval of the customer, install the air conditioner in a place that satisfies the following conditions. • Place where the unit can be installed horizontally. • Place where a sufficient servicing space can be ensured for safety maintenance and check. •...
  • Page 11: Installation Space

    Concealed Duct High Static Pressure „ Installation space Reserve space required for maintenance the indoor unit and service work. Check port with carrying in port 600x600 <Installation example> Air outlet chamber Duct hose Air flow direction REQUIREMENT 1. Attach the optional accessories (drain-up kit etc.) on the unit before installing the unit. Also, set the check port with carrying in port to the side surface of the unit except air inlet panel.
  • Page 12: Installation

    Concealed Duct High Static Pressure INSTALLATION • Install the air conditioner certainly to sufficiently withstand the weight. • If the strength is insufficient, the unit may fall down resulting in human injury. • Perform a specified installation work to guard against strong wind or earthquake. •...
  • Page 13: Installation Of Indoor Unit

    Concealed Duct High Static Pressure „ Installation of hanging bolt • Consider the piping/wiring after the unit is hung when determining the location of the indoor unit installation and orientation. • After the location of the indoor unit installation has been determined, install hanging bolts.
  • Page 14 Concealed Duct High Static Pressure „ Diagrams for making connecting flanges The connecting flange (Incl. the fixing screw) is not supplied to the indoor unit. When the connecting flange is necessary, produce them in locally. Drawing figure is as follows. (Material: Galvanized steel plate, thickness of 1.6 mm) <Air outlet port flange>...
  • Page 15: Duct Design

    Concealed Duct High Static Pressure „ Duct design 1. In order to prevent short circuits, design the duct installation, so that the intake and discharge openings are not adjacent to each other. 2. The indoor unit does not have a built-in air filter. Make sure to set up the filter chamber etc. and install the air filter (Locally procured).
  • Page 16: Fan Characteristics

    Concealed Duct High Static Pressure FAN CHARACTERISTICS Current value as a criterion, adjust the air volume value to become within the range of the chart below. <RAV-SM2242 Type> Standard air volume: 3600m³/h 2800 3000 2880 3200 Lower limit of air volume 15-EN 3400 3800...
  • Page 17 Concealed Duct High Static Pressure <RAV-SM2802 Type> Standard air volume: 4200m³/h 3200 3400 3800 3360 3600 4000 Lower limit of air volume Air volume (m³/h) REQUIREMENT Add a air volume damper to the air supply duct, and adjust the air volume in the range from 80% to 120% of the standard air volume.
  • Page 18 Concealed Duct High Static Pressure „ Wire connection change of fan motor This duct is composed of 3 fan motors. To change external static pressure by duct resistance, connect the 3 connectors of the orange lead wires that are connected to the underside of the fan tap changing terminal block to the same number (F1, F2 or F3) terminal.
  • Page 19: Drain Piping Work

    Concealed Duct High Static Pressure DRAIN PIPING WORK Following the Installation Manual, perform the drain piping work that water is properly drained, and apply a heat insulation not to cause a dew condensation. Inappropriate piping work may cause the water leakage in the room and wet of furniture. REQUIREMENT •...
  • Page 20 Concealed Duct High Static Pressure „ Pipe material, size and insulator The following materials for piping work and insulating process are procured locally. Hard vinyl chloride pipe socket for VP25 Pipe material Hard vinyl chloride pipe VP25 (Nominal outer diameter Ø32mm) Insulator Foamed polyethylene foam, thickness: 10mm or more „...
  • Page 21: Check The Draining

    Concealed Duct High Static Pressure „ Check the draining Check if the water can flow out properly during the test run. Also, check if no water leakage from the piping connection port. REQUIREMENT • Do drain test even if installation of heating season. •...
  • Page 22 Concealed Duct High Static Pressure „ Heat insulating process • After drain check, covering the heat insulator for drain connecting section, wrap the drain pipe with heat insulator (Locally procured) without clearance from the end of the drain pipe connecting port of the indoor unit. Drain pipe connecting port Indoor unit 21-EN...
  • Page 23: Refrigerant Piping And Evacuating

    Concealed Duct High Static Pressure REFRIGERANT PIPING AND EVACUATING „ Refrigerant Piping 1. If the outdoor units are to be mounted on a wall, make sure that the supporting platform is sufficiently strong. The platform should be designed and manufactured to maintain its strength over a long period of time, and sufficient consideration should be given to ensuring that the outdoor unit will not fall.
  • Page 24: Tightening Connection

    Concealed Duct High Static Pressure Tightening connection CAUTION Do not apply excessive torque. Otherwise, the nut may crack depending on the conditions. Outer dia. of copper pipe 12.7 mm (dia.) M Tightening torque of flare pipe connections Pressure of R410A is higher than that of R22. (Approx.
  • Page 25: Gas Leak Check

    Concealed Duct High Static Pressure Refrigerant amount to be added For addition of the refrigerant, add refrigerant “R410A” referring to the attached Installation Manual of outdoor unit. Be sure to use a scale to charge the refrigerant of specified amount. REQUIREMENT •...
  • Page 26: Electrical Connection

    Concealed Duct High Static Pressure ELECTRICAL CONNECTION WARNING 1. Using the specified wires, ensure to connect the wires, and fix wires securely so that the external tension to the wires do not affect the connecting part of the terminals. Incomplete connection or fixation may cause a fire, etc.
  • Page 27: Wire Connection

    Concealed Duct High Static Pressure „ Wire connection REQUIREMENT • Be sure to connect the wires matching the terminal numbers. Incorrect connection causes a trouble. • Be sure to pass the wires through the bushing of wire connection holes of the indoor unit. •...
  • Page 28: Remote Controller Wiring

    Concealed Duct High Static Pressure R (L) S (N) Indoor fan power supply wire System interconnecting wire „ Remote Controller Wiring • Strip off approx. 9mm the wire to be connected. • Non polarity, 2 core wire is used for wiring of the remote controller.
  • Page 29: Applicable Controls

    Concealed Duct High Static Pressure APPLICABLE CONTROLS REQUIREMENT • When you use this air conditioner for the first time, it takes approx. 5 minutes until the remote controller becomes available after power-on. This is normal. <When power is turned on for the first time after installation>...
  • Page 30: Power Saving Mode

    Concealed Duct High Static Pressure Procedure When settings have been completed, push determine the settings. When button is pushed, “SETTING” flashes and then the display content disappears and the air conditioner enters the normal stop mode. (While “SETTING” is flashing, no operation of the remote controller is accepted.) „...
  • Page 31 Concealed Duct High Static Pressure „ Remote controller switch monitoring function This function is available to call the service monitor mode from the remote controller during a test run to acquire temperatures of sensors of the remote controller, indoor unit, and outdoor unit.
  • Page 32: Group Control

    Concealed Duct High Static Pressure „ Group control Group control for system of multiple units One remote controller can control up to 8 indoor units as a group. M Group control in single system Outdoor unit Outdoor unit Indoor unit Indoor unit Remote controller •...
  • Page 33 Concealed Duct High Static Pressure Procedure example 1 Manual address setup procedure While the operation stops, change the setup. (Be sure to stop the operation of the unit.) Procedure Push simultaneously buttons for 4 seconds or more. After a while, the display part flashes as shown below. Check the displayed CODE No.
  • Page 34 Concealed Duct High Static Pressure Procedure If there is other indoor unit to be changed, repeat procedure to change the setup. When the above setup has finished, push the indoor UNIT No. before change of setup, specify CODE No. [12], [13], [14] in order with TEMP. and then check the changed contents.
  • Page 35 Concealed Duct High Static Pressure „ 8°C Operation Pre-heating operation can be set for cold regions where room temperature drops to below zero. Procedure Push simultaneously buttons for 4 seconds or more when the air conditioner is not working. After a while, the display part flashes as shown below. Check the Displayed CODE No.
  • Page 36: Test Run

    Concealed Duct High Static Pressure TEST RUN „ Before test run • Before turning on the power supply, carry out the following procedure. 1) Using 500V-megger, check that resistance of 1M: or more exists between the terminal block 1 to 3 and the earth (grounding).
  • Page 37: Maintenance

    Concealed Duct High Static Pressure MAINTENANCE When connecting a return air duct to the unit, the cleaning method of the air filter differs according to the construction of duct end. Ask a qualified installer or qualified service person. <Daily maintenance> Cleaning of air filter 1.
  • Page 38 Concealed Duct High Static Pressure Maintenance List Part Heat exchanger Indoor/outdoor Indoor/outdoor Fan motor Filter Indoor/outdoor Air inlet/outlet grilles Drain pan Ornamental panel, louvres Outdoor Exterior 37-EN Unit Check (visual/auditory) • Dust/dirt clogging, scratches • Sound • Dust/dirt, breakage Indoor •...
  • Page 39: Troubleshooting

    Concealed Duct High Static Pressure TROUBLESHOOTING „ Confirmation and check When an error occurred in the air conditioner, an error code and indoor UNIT No. appear on the display part of the remote controller. The error code is only displayed during the operation. If the display disappears, operate the air conditioner according to the following “Confirmation of error log”...
  • Page 40: Error Codes

    Concealed Duct High Static Pressure „ Error codes and parts to be checked Wired remote controller display Main defective parts Indication No header remote controller Remote controller communication error Remote controller transmission error Indoor unit-remote controller regular communication error Indoor unit-outdoor unit serial communication error IPDU-CDB communication error Duplicated indoor addresses...
  • Page 41 Concealed Duct High Static Pressure Wired remote controller Main defective parts display Indication LAN communication error Other outdoor unit error Abnormal external input into indoor unit (interlock) Phase sequence error, etc. Indoor unit fan error Outdoor unit discharge temp. error Outdoor unit high-pressure system error Open phase detected...

This manual is also suitable for:

Rav-sm2802dt-e

Table of Contents