Self-Clean Operation; Save Operation; Auto Restart - Toshiba RAV-SM566KRT-E Service Manual

Air conditioner split type
Hide thumbs Also See for RAV-SM566KRT-E:
Table of Contents

Advertisement

No.
Item
19

Self-clean operation

(Dry operation)

Save operation

20
(Wired remote
controller specific
operation)

21 Auto restart

Outline of specifications
1) When cooling operation mode (AUTO COOL, COOL, DRY) stopped, the following
three self-clean operations are performed.
Compressor
Self-clean
ON period
operation period
0 to 10 min.
None
10 to 60 min.
1 hour
60 min. to
2 hours
2) During operation of self-clean,
remote controller screen. However the operation lamp
(Green LED) goes off.
3) To stop the self-clean operation, push twice the
[ON/OFF] button on the remote controller continuously.
(Stop the operation as compressor ON time in the table
above: 10 minutes or below.)
4) When the follower unit executes self-clean operation in the
group connection, the segment of
wired remote controller screen via master unit.
∗ If self-clean operation is not used, set invalidity
(does not use) of the self-clean operation by changing
[0001 (At shipment) of Item code (DN) [D3] to [0000].
∗ To erase the
display during operation of self-clean,
change Item code [D4] from [0000: Display
(At shipment)] to [0001: Non-display].
1) Turn on
SAVE
button on the wired remote controller.
2) During operation of save operation,
remote controller.
3) During save operation, the current release control is performed
with the restriction ratio set in EEPROM on the outdoor unit.
4) The restriction ratio can be set by keeping
pushed for 4 seconds or more on the remote controller.
5) When validating the save operation, the next operation starts
with save operation valid because contents are held even
when operation stops, operation mode changes or power
supply is reset.
6) The restriction ratio can be set by changing the setup data of
CODE No. (DN) [C2] in the range of 50 to 100%
(every 1%, Setting at shipment: 75%).
1) Object
It restarts the operation automatically after resetting the
unexpected stop of power supply such as power failure.
2) Contents
After returning from a power failure, the auto restart function
reads the operation status from EEPROM and then restarts
the operation automatically according to the operation
contents.
3) Setup of function exchange by wired remote controller
CODE No. (DN): 28
SET DATA
Auto restart
None (At shipment)
FAN
450 rpm
lights on the wired
is displayed on the
lights on the wired
SAVE
0000
0001
Provided
36
FILE NO. SVM-12004
Remarks
Louver
Position of 15° from all closes
On the remote control-
ler before the wired
remote controller
(RBC-AMT31E),
Self-clean operation
display is not output.
And it is not also on
the wireless remote
controller.
It is recognized as
[STOP] from the
remote monitor side.
Carry out setting
operation during stop of
the unit; otherwise the
unit stops operation.
For the setup operation,
refer to "How to set up
button
contents of save
operation" of
"10. SETUP AT LOCAL
SITE AND OTHERS".