10-8-7. Central Control Address Number Setting

To connect an indoor unit to the central control remote controller, an address number for central control must
be set.
• An address number for central control is indicated as the refrigerant line number of the remote controller.

1 Setting by Remote Controller on Indoor Unit Side

<Procedure> Perform the following steps in the operation OFF mode.
1
VENT
Push
TEST
and
When group control is going, UNIT No.
lected. At this time, the fans of all the selected indoor units start running. (Fig. 1)
Maintain this state without pushing
For individual remote controllers without group control, a refrigerant line address and an indoor unit
address are indicated.
2
!
Specify code
with
3
Choose setting data with
Table 1 shows setting data.
4
Push
SET
Indication on the LCD shows normal operation.
• To change an item for setting, return to
5
Push
TEST
to return to the normal indication.
on the remote controller simultaneously for 4 seconds or more.
is displayed first, and all indoor units in the group are se-
UNIT LOUVER
.
TEMP.
buttons.
buttons.
TIME
2
.
82
FILE NO. SVM-12004
(Fig.1)
CODE No.
SET DATA
SETTING
UNIT No.
R.C.
No.
ON / OFF
AN
VE
FILTER
RESET
TEST
SET
CL
SWING/FIX
UNIT LOUVER
4
3
2 5
Table 1
Address No. for
Setting data
central control
0001
1
0002
2
0003
3
|
|
0064
64
Not set
0099
(factory setting)
MODE
VENT
1