Applied control for outdoor unit

The outdoor fan high static pressure support and priority operation mode setting (cooling / heating / number of
units / or priority indoor unit) functions are made available by setting relevant switches provided on the interface
P.C. board of the outdoor unit.

7-1. Outdoor fan high static pressure shift

Purpose / characteristics
This function is used when connecting a duct to the discharge port of an outdoor unit (as part of, for example,
unit installation on the floor by floor installation.)
Setup
Turn ON the DIP switch [SW10, Bit 2] provided on the interface P.C. board of the outdoor unit.
Specifications
Increase the speed of the propeller fan units on the outdoor fan to allow the installation of a duct with a
maximum external static pressure not greater than specified in the table below.
Table 1: Maximum External Static Pressures of Outdoor Units
For Europe and Turkey model
M
o
d
l e
Maximum external static pressure
Outdoor unit air flow
1 *
For China model
M
o
d
l e
Maximum external static pressure
Outdoor unit air flow
1 *
*1 Calculate duct resistance from outdoor unit air flow.

7-2. Priority operation mode setting

Purpose / characteristics
This function allows switching between priority cooling and priority heating.
Four patterns of priority operation mode setting are available as shown in the table below. Select a suitable priority
mode according to the needs of the customer.
Setup
CAUTION
In the case of the priority indoor unit mode, it is necessary to set up the specific indoor unit chosen for priority operation
(a single unit only).
(1) Outdoor unit setup method
SW11
Bit 1
Bit 2
OFF
OFF
ON
OFF
OFF
ON
ON
ON
M
C
P (
(
m
/
3
M
C
P (
(
m
/
3
Priority heating (factory default)
Priority cooling
Priority operation based on No. of units in operation (priority given to the operation mode with the
largest share of units in operation)
Priority indoor unit (priority given to the operation mode of the specific indoor unit set up for priority
operation)
- Y
MHP0806HS8
MHP1006HS8
) a
20
) h
7200
- Y
MHP0806HT8
MHP0906HT8
) a
20
) h
7200
Operation
36
52
20
7620
MHP1006HT8
20
20
8160
8580