Recharging Of Refrigerant; Configuration Of Refrigerant Charging - Toshiba RAV-SM566KRT-E Service Manual

Air conditioner split type
Hide thumbs Also See for RAV-SM566KRT-E:
Table of Contents

Advertisement

6-4. Recharging of Refrigerant

When it is necessary to recharge refrigerant, charge the specified amount of new refrigerant according to the
following steps.
Recover the refrigerant, and check no refrigerant
remains in the equipment.
Connect the charge hose to packed valve service port
at the outdoor unit's gas side.
Connect the charge hose to the vacuum pump adapter.
Open fully both packed valves at liquid and gas sides.
Place the handle of the gauge manifold Low in the
fully opened position, and turn on the vacuum pump's
power switch.
Then, evacuating the refrigerant in the cycle.
1. Never charge refrigerant exceeding the specified amount.
2. If the specified amount of refrigerant cannot be charged, charge refrigerant bit by bit in COOL mode.
3. Do not carry out additional charging.
When additional charging is carried out if refrigerant leaks, the refrigerant composition changes in the
refrigeration cycle, that is characteristics of the air conditioner changes, refrigerant exceeding the specified
amount is charged, and working pressure in the refrigeration cycle becomes abnormally high pressure, and
may cause a rupture or personal injury.
Refrigerant cylinder
(With siphon pipe)
Electronic balance for refrigerant charging
CAUTION
(INDOOR unit)
Check valve
Open/Close valve
for charging
Fig. 6-4-1 Configuration of refrigerant charging
When the compound gauge's pointer has indicated
–0.1 Mpa (–76 cmHg), place the handle Low in the
fully closed position, and turn off the vacuum pump's
power switch.
Keep the status as it is for 1 to 2 minutes, and ensure
that the compound gauge's pointer does not return.
Set the refrigerant cylinder to the electronic balance,
connect the connecting hose to the cylinder and the
connecting port of the electronic balance, and charge
liquid refrigerant.
(For refrigerant charging, see the figure below.)
(Liquid side)
Opened
(Gas side)
Closed
Service port
23
FILE NO. SVM-12004
(OUTDOOR unit)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents