Blower Performance - Lennox G40DF Series Installation Instructions Manual

G40df(x) series
Hide thumbs Also See for G40DF Series:
Table of Contents

Advertisement

Flue And Chimney
1 − Check flue pipe, chimney and all connections for tight-
ness and to make sure there is no blockage.
2 − Check unit for proper draft.
3 − Is pressure switch closed? Obstructed flue will cause
unit to shut off at pressure switch. Check flue and outlet
for blockages.
4 − Reset manual flame rollout switches on burner box
cover.
Failure To Operate
If the unit fails to operate, check the following:

Blower Performance

NOTE − All air data is measured external to unit with 1 in. cleanable filter (not furnished − field provided) in place.
G40DF−24A−045 PERFORMANCE
External
Air Volume / Watts at Different Blower Speeds
Static
High
Pressure
cfm
Watts
in. w.g.
0.00
1200
417
0.05
1185
410
0.10
1165
402
0.15
1145
396
0.20
1125
390
0.25
1105
382
0.30
1080
374
0.40
1020
357
0.50
960
342
0.60
900
330
0.70
815
313
0.80
685
289
0.90
560
271
G40DF−36A−070 PERFORMANCE
Air Volume / Watts at Different Blower Speeds
External
Medium−
Static
High
Pressure
in. w.g.
cfm Watts cfm Watts cfm Watts cfm Watts
0.00
1475 616 1345 554 1150 495
0.05
1450 606 1320 543 1140 481
0.10
1425 595 1300 532 1125 466
0.15
1395 585 1275 521
0.20
1375 574 1255 510 1105 437
0.25
1345 563 1230 494 1090 428
0.30
1320 552 1205 478 1075 418
0.40
1250 528 1150 455 1040 395
0.50
1200 508 1095 432 1000 374
0.60
1110
475 1035 409
0.70
1030 455
970
0.80
960
434
875
0.90
770
389
715
Medium
Low
cfm
Watts
cfm
Watts
1060
367
830
1040
360
820
1025
353
810
1010
346
795
990
338
775
980
335
765
965
331
750
920
319
710
875
306
650
810
290
620
690
272
565
620
259
465
510
238
395
Medium−
Low
High
Low
990
985
975
1115
452
970
965
955
945
920
880
950
354
830
390
855
338
720
359
735
299
665
321
665
278
590
1 − Is the thermostat calling for heat?
2 − Are access panels securely in place?
3 − Is the main disconnect switch closed?
4 − Is there a blown fuse?
5 − Is the filter dirty or plugged? Dirty or plugged filters will
cause the limit control to shut the unit off.
6 − Is gas turned on at the meter?
7 − Is the manual main shut-off valve open?
8 − Is the internal manual shut-off valve open?
9 − Is the unit ignition system in lock out? If the unit locks out
again, inspect the unit for blockages.
G40DF−36B−090 PERFORMANCE
Air Volume / Watts at Different Blower Speeds
External
Static
Pressure
in. w.g.
cfm Watts cfm Watts cfm Watts cfm Watts
278
0.00
1600 608 1410 526 1165 436
274
0.05
1580 599 1400 518 1165 428
270
0.10
1560 589 1390 509 1160 420
265
0.15
1530 573 1370 497 1155 413
260
0.20
1495 556 1350 485 1150 406
257
0.25
1465 544 1325 473 1135 398
254
0.30
1430 532 1300 460 1125 389
244
0.40
1370 509 1250 438 1095 373
234
0.50
1295 482 1200 420 1055 355
231
0.60
1215 456 1140 397 1010 343
221
0.70
1140 437 1055 371
203
0.80
1000 401
190
0.90
900
G40DF−48C−090 PERFORMANCE
Air Volume / Watts at Different Blower Speeds
External
Static
Pressure
in. w.g.
cfm Watts cfm Watts cfm Watts cfm Watts
415
0.00
2040 749 1850 657 1595 562 1325 466
407
0.05
2000 727 1825 638 1575 547 1340 460
398
0.10
1955 704 1800 619 1555 532 1350 453
390
0.15
1920 692 1770 602 1540 518 1340 441
381
0.20
1885 679 1740 585 1525 503 1330 428
371
0.25
1845 662 1700 568 1500 488 1300 414
360
0.30
1800 645 1665 551 1475 473 1270 399
346
0.40
1695 606 1585 517 1415 448 1225 378
331
0.50
1600 570 1490 485 1335 414 1170 360
313
0.60
1495 540 1405 457 1250 389
280
0.70
1380 509 1300 426 1165 367 1025 316
266
0.80
1250 478 1160 390 1025 331
244
0.90
1095 439 1030 360
Page 26
Medium−
Medium−
High
High
Low
915
950
342
850
374
820
313
740
Medium−
Medium−
High
High
Low
925
Low
965
355
965
351
970
346
965
341
965
335
955
329
945
323
935
313
900
302
860
285
313
800
272
295
730
251
272
− − −
− − −
Low
1110
337
− − −
− − −
307
− − −
− − −