If retro-reflectors or very shiny surfaces, such as polished or enameled metals or
ceramics, may possibly be present in the scanning plane, the following table applies:
Addition Z
reflectors or very shiny,
surface-treated materials
(e.g. metals and ceramics)
are present in the scanning
plane
Z = Z
+ Z
SM
Z
= Required detection zone addition, in mm
Z
= Measurement error of the scanner, in mm
SM
Z
= Addition for considering reflectors, in mm
REFL
5.4

Safeguarding Stationary Danger Zones

Please comply with the safety notes in Chapter 3.
5.4.1

The Purpose of Safeguarding

is for protection:
to protect people when entering a danger zone
to protect people from reaching a danger point with their extremities
to protect objects from the danger of collision due to variable machine or part
movements.
5.4.2

Mounting Position

The SIMATIC FS600 Laser Scanner can be mounted either in a stationary position (e.g.
on a wall or a machine) or on moving parts (e.g. machine table).
The qualified installer must ensure that the mounting position of the SIMATIC FS600
Laser Scanner allows the danger zone to be monitored completely.
If a restart button is being used, make certain that the entire detection zone area can be
viewed by the person pressing the button. It must not be possible to activate the button
from the danger area.
Refer to the safety notes in Chapter 3.6 with regard to lateral access into the danger
zone.
if retro-
REFL
REFL
0 mm
for reflectors more than 1.2 m behind the detection
zone line
110 mm
for reflectors up to 1.2 m behind the detection zone
line