Troubleshooting

START
Gas Supply ON
YES
Pilot Lights with
Piezo Ignitor
YES
Pilot Stays Lit
YES
Pilot Lights
Main Burner
YES
System OK
FP396b
HV standing pilot
troubleshoot
RFSDV24/34 Freestanding Direct Vent Gas Fireplace
Remove Glass Panel Before Servicing.
CHECK
• Supply line hooked up
NO
• Shutoff valve open
• Lockout has engaged. Wait
60 seconds and try again.
• For spark at electrode while
NO
depressing Piezo - 1/8" gap to
pilot hood needed.
• All wiring connections
• Replace Piezo ignitor
• For air in lines
• Thermopile needs a minimum
325mV. Adjust pilot flame height.
• All Wiring connections
• Replace thermopile
NO
• Thermocouple needs a minimum
14mV.
• Defective valve. Turn to pilot,
meter should read greater than
100mV. If not, replace.
• Valve is turned on
• Wall switch is not turned on.
NO
Watch for grounded wires!
• Thermopile needs a minimum
325mV.
• Plugged burner orifice.
FP396a