Electrical Data -Without Powered Convenience Outlet - York BQ240 Technical Manual

Sunline 2000 single package air-to-air heat pumps 20 nominal tons, 8.8 eer
Hide thumbs Also See for BQ240:
Table of Contents

Advertisement

036-21489-001-C-1004
TABLE 11: ELECTRICAL DATA -WITHOUT POWERED CONVENIENCE OUTLET
COMPRESSORS
MODEL
VOLTAGE
RLA
TONNAGE
EACH
208
16.7
230
16.7
BQ240
460
9.6
575
6.4
Note 1: Maximum HACR breaker of the same amp size is acceptable.
Note 2: Only 18kW of the 36 or 54kW, or only 36kW of the 72kW electric heat can be simultaneously energized with the mechanical
heating. The full heater kW operates only if both compressors are locked out.
Unitary Products Group
ID
OD FAN
BLOWER
MOTORS
LRA
MOTOR
FLA EACH
EACH
FLA
150
4.5
19.4
150
4.3
21.0
75
2.2
9.7
62
1.7
7.8
HEATER OPTION
CONV
OUTLET
2
MODEL KW
STAGES AMPS
AMPS
-
0.0
E18
13.5
0.0
E36
27.0
E54
40.6
E72
54.1
-
0.0
E18
18.0
0.0
E36
36.0
E54
54.0
E72
72.0
-
0.0
E18
18.0
0.0
E36
36.0
E54
54.0
E72
72.0
-
0.0
E18
18.0
0.0
E36
36.0
E54
54.0
E72
72.0
MIN.
CIRCUIT
AMPACITY
(AMPS)
-
-
100.1
1
37.5
146.9
2
75.1
146.9
2
112.6
165.1
2
150.1
193.7
-
-
101.7
1
43.3
155.8
2
86.6
155.8
2
129.9
156.2
2
173.2
209.9
-
-
54.9
1
21.7
82.0
2
43.3
82.0
2
65.0
82.0
2
86.6
109.1
-
-
38.8
1
17.3
60.4
2
34.6
60.4
2
52.0
61.7
2
69.3
82.1
MAX.
FUSE/
1
BRKR
SIZE
(AMPS)
110
150
150
175
200
110
175
175
175
225
60
90
90
90
110
45
70
70
70
90
23

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sunline 2000

Table of Contents