MBE/MBR
BLOWER CABINET
INSTALLATION INSTRUCTIONS
THIS PRODUCT CONTAINS ELECTRONIC COMPONENTS WHICH REQUIRE A
DEFINITE GROUND. PROVISIONS ARE MADE FOR CONNECTION OF THE
GROUND. A DEDICATED GROUND FROM THE MAIN POWER SUPPLY OR
AN EARTH GROUND MUST BE PROVIDED.

INTRODUCTION

This booklet contains the installation and operating instruc-
tions for your modular blower cabinet. All warnings and pre-
cautions within this booklet must be observed. Improper in-
stallation can result in unsatisfactory operation or dangerous
conditions and void the warranty. Read this booklet and any
instructions packaged with accessories prior to installation.
Give this booklet to the user and explain its provisions. The
user should retain this booklet for future reference.

CHECKING PRODUCT RECEIVED

Upon receiving the unit, inspect it for damage from shipment.
Claims for damage, either shipping or concealed, should be
filed immediately with the shipping company. Check the unit
model number, specifications, electrical characteristics and
accessories to determine if they are correct. In the event an
incorrect unit is shipped, it must be returned to the supplier
and must NOT be installed. The manufacturer assumes no
responsibility for installation of incorrectly shipped units.

REPLACEMENT PARTS

ORDERING PARTS

When reporting shortages or damages, or ordering repair parts,
give the complete unit model and serial numbers as stamped
on the unit's nameplate.
Replacement parts for this appliance are available through your
contractor or local distributor. For the location of your nearest
distributor, consult the white business pages, the yellow page
section of the local telephone book or contact:
SERVICE PARTS DEPARTMENT
GOODMAN MANUFACTURING COMPANY, L.P.
5151 SAN FELIPE, SUITE 500
HOUSTON, TEXAS 77056
(713) 861 – 2500

IMPORTANT SAFETY INSTRUCTIONS

RECOGNIZE SAFETY SYMBOLS, WORDS, AND LABELS

The following symbols and labels are used throughout this
manual to indicate immediate or potential hazards. It is the
owner's responsibility to read and comply with all safety infor-
mation and instructions accompanying these symbols. Fail-
ure to heed safety information increases the risk of property
damage, product damage, personal injury or death.
Goodman Manufacturing Company, L.P. © 2004-2009
5151 San Felipe, Suite 500, Houston, TX 77056
www.goodmanmfg.com -or- www.amana-hac.com
P/N: IO-239E
Date: July 2009
HIGH VOLTAGE!
Disconnect ALL power before servicing.
Multiple power sources may be present.
Failure to do so may cause property damage,
personal injury or death.
Installation and repair of this unit should be performed
ONLY
by individuals meeting the requirements of an
"entry level technician" as specified by the Air
Conditioning, Heating, and Refrigeration Institute
(AHRI). Attempting to install or repair this unit without
such background may result in product damage,
personal injury or death.
CARBON MONOXIDE POISONING HAZARD
Special Warning for Installation of Furnace or Air Handling Units in
Enclosed Areas such as Garages, Utility Rooms or Parking Areas
Carbon monoxide producing devices (such as an automobile, space
heater, gas water heater, etc.) should not be operated in enclosed areas
such as unventilated garages, utility rooms or parking areas because of
the danger of carbon monoxide (CO) poisoning resulting from the exhaust
emissions. If a furnace or air handler is installed in an enclosed area such
as a garage, utility room or parking area and a carbon monoxide producing
device is operated therein, there must be adequate, direct outside
ventilation.
This ventilation is necessary to avoid the danger of CO poisoning which
can occur if a carbon monoxide producing device continues to operate in
the enclosed area. Carbon monoxide emissions can be (re)circulated
throughout the structure if the furnace or air handler is operating in any
mode.
CO can cause serious illness including permanent brain damage or death.

GENERAL INFORMATION

The MBR/MBE Blower Cabinets are used in combination with
a cased evaporator coil. This combination of blower and coil
functions as the indoor part of a split air-conditioning system,
and may be matched with a remote condensing or heat pump
unit. The blower cabinet can also function as an electric fur-
nace when used with an electric heater.
NOTE: The electric heating elements for electric furnace in-
stallation are not shipped with the cabinet and are field-installed.
B10259-216
-

Advertisement

Table of Contents
loading

Summary of Contents for Goodman MBE Series

  • Page 1: Introduction

    MBE/MBR Goodman Manufacturing Company, L.P. © 2004-2009 5151 San Felipe, Suite 500, Houston, TX 77056 BLOWER CABINET www.goodmanmfg.com -or- www.amana-hac.com INSTALLATION INSTRUCTIONS P/N: IO-239E Date: July 2009 THIS PRODUCT CONTAINS ELECTRONIC COMPONENTS WHICH REQUIRE A DEFINITE GROUND. PROVISIONS ARE MADE FOR CONNECTION OF THE GROUND.
  • Page 2: Table Of Contents

    Contents INTRODUCTION ............................1 CHECKING PRODUCT RECEIVED ......................1 REPLACEMENT PARTS ..........................1 ORDERING PARTS ..................................1 IMPORTANT SAFETY INSTRUCTIONS.......................1 RECOGNIZE SAFETY SYMBOLS, WORDS, AND LABELS ......................1 GENERAL INFORMATION ..........................1 CLEARANCES AND ACCESSIBILITY ............................3 INSULATION ....................................3 INSTALLATION INSTRUCTIONS ........................3 BLOWER WITH CASED EVAPORATOR COIL INSTALLATION .....................
  • Page 3: Clearances And Accessibility

    3. Attach supply ductwork. Seal connections between unit Systems should be properly sized by heat gain and loss cal- and ductwork as required to reduce/eliminate air leak- culations made according to methods of the Air Conditioning age. Contractors Association (ACCA) or equivalent. It is the contractor’s responsibility to ensure the system has adequate 4.
  • Page 4: Horizontal Installation

    HORIZONTAL INSTALLATION FRONT VIEW SIDE VIEW For horizontal installations, the coil cabinet must be upstream of the blower cabinet (Figures 5 and 6). NOTE: All panels should be in place when installing the unit. 1. Set the unit near its final installation place. The unit must be supported along the entire length of the unit.
  • Page 5: Low Voltage Wiring

    Note: The two stage configurations are illustrated to detail con- nections to the two capacity condensing units and heat pumps. An equivalent thermostat can be used in place of the Goodman thermostat part number. The GMC thermostats listed are mercury type.
  • Page 6: Thermostat "Fan Only" Mode

    TWO STAGE HEATING Model Switch 1 Switch 2 Electric Heat CFM When using staged electric heat, cut jumper PJ4 on the con- 1200 trol board. 1000 MBE1200 THERMOSTAT WIRING Use thermostat wiring diagram Figures 7 through 37 and 1600 those provided with the thermostat when making these con- 1400 nections.
  • Page 7 HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING. WARNING MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. R O O M T H E R M O S T A T # 1 8 G A .
  • Page 8 HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING. WARNING MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. FIGURE 9 SYSTEM COMPOSITE DIAGRAM 800-2000 10 KW & BELOW CONVENTIONAL ROOM THERMOSTAT HEAT PUMP #18 GA.
  • Page 9: Single Stage Cooling With Single Or Two Stage Heating

    HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING. WARNING MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. SINGLE STAGE COOLING WITH SINGLE OR TWO STAGE HEATING ROOM THERMOSTAT CONDENSING HUMIDISTAT (OPTIONAL) UNIT NOTES: SEE NOTE 4...
  • Page 10: Heat Pump With Single Or Two-Stage Heating (Options For Emergency Heat)

    HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING. WARNING MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. ROOM OUTDOOR THERMOSTAT THERMOSTAT HUMIDISTAT CONDENSING (OPTIONAL) UNIT NOTES: SEE NOTE 4 1.) Y/Y2 ENABLES HI SPD FAN COOLING THERMOSTATS HUMIDISTAT E\W1...
  • Page 11 HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING. WARNING MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. REMOVE PRODUCTION WIRE Y1-O Figure 15 REMOVE PRODUCTION WIRE Y1-O Figure 16 Wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring.
  • Page 12 HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING. WARNING MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. REMOVE PRODUCTION WIRE Y1-O Figure 17 (OPTIONAL) YCON REMOVE W/W2 PRODUCTION OUTDOOR WIRE Y1-O YCON 24 VAC 3.) OT1 PJ4 AND 0T2 PJ2 MUST BE CUT...
  • Page 13: Two-Stage Cooling With Conventional Two-Stage Thermostat

    HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING. WARNING MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. TWO-STAGE COOLING WITH CONVENTIONAL TWO-STAGE THERMOSTAT ROOM THERMOSTAT 2-SPD CONDENSING HUMIDISTAT UNIT (OPTIONAL) SEE NOTE 4 NOTES: THERMOSTATS HUMIDISTAT...
  • Page 14 HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING. WARNING MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. ROOM THERMOSTAT 2-SPD CONDENSING HUMIDISTAT UNIT (OPTIONAL) SEE NOTE 4 NOTES: 1.) Y1 ENABLES LO SPD FAN COOLING Y/Y2 ENABLES HI SPD FAN COOLING 2.) E/W1 ENABLES HI SPD FAN HEATING 3.) IF OT1 PJ4 JUMPER IS CUT E/W1 ENABLES...
  • Page 15: Heat Pump With Single Or Two Stage Heating With Conventional Thermostat (Options For Emergency Heat)

    HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING. WARNING MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. HEAT PUMP WITH SINGLE OR TWO STAGE HEATING WITH CONVENTIONAL THERMOSTAT (OPTIONS FOR EMERGENCY HEAT) ROOM HEATPUMP THERMOSTAT...
  • Page 16 4.) CUT HUM PJ6 JUMPER IF USING HUMIDISTAT STAT OPENS ON HUMIDITY RISE 5.) DIP SWITCH #4 MUST BE IN THE "ON" POSITION PN. B1368274 GOODMAN MFG. CO. L.P. 2nd STAGE HEATER 1ST STAGE HEATER HEATPUMP - 2 STG EMHT 2 STAG AUX - 1 OUTDOOR T-STAT...
  • Page 17: Speed Heat Pump With Single Or Two-Stage Heating (Options For Emergency Heat) With Conventional Two-Stage Thermostat

    4.) CUT HUM PJ6 JUMPER IF USING HUMIDISTAT STAT OPENS ON HUMIDITY RISE 5.) DIP SWITCH #4 MUST BE IN THE "ON" POSITION PN. B1368274 GOODMAN MFG. CO. L.P. 2nd STAGE HEATER 1ST STAGE HEATER HEATPUMP - 2 STG EMHT 1 STG AUX - 1 OUTDOOR T'STAT...
  • Page 18 HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING. WARNING MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. ROOM 2 SPD HEATPUMP THERMOSTAT HUMIDISTAT HEATPUMP (OPTIONAL) CONDENSER YCON COM SEE NOTE 4 HUMIDISTAT THERMOSTATS REMOVE...
  • Page 19 HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING. WARNING MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. ROOM 2-SPD HEATPUMP THERMOSTAT HUMIDISTAT HEATPUMP (OPTIONAL) CONDENSER YCON COM SEE NOTE 4 THERMOSTATS HUMIDISTAT REMOVE E\W1...
  • Page 20: Two Stage Cooling With Conventional Two Stage Thermostat (Enclosed With Add On 1N006 Diodes)

    HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING. WARNING MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. OUTDOOR ROOM THERMOSTAT 2-SPD HEATPUMP THERMOSTAT HUMIDISTAT HEATPUMP (OPTIONAL) CONDE NSER YCON COM SEE NOTE 4 THERMOSTATS HUMIDISTAT REMOVE...
  • Page 21: Required

    OUTDOOR HEATPUMP CON DENSER YCON COM 24 VAC PLEASE REFER TO MANUAL FOR PROPER DIP SW ITCH GOODMAN MFG. CO. L.P. CONFIGURATION. GOODMAN MFG. CO. L.P. 24 V Y/Y2 2ND STAGE HEATER YLO/Y1 1ST STAGE HEATER NOTES: CUT OT2 PJ2 FOR 2-STAGE HEAT OPERATION 1.) STAT OPENS ON HUMIDITY RISE...
  • Page 22: Troubleshooting Encoded Two Stage Cooling Thermostats Options

    HEATPUMP YCON COM 24 VAC PLEASE REFER TO MANUAL FOR PROPER DIP SW ITCH PN. B1368271 REV. A GOODMAN MFG. CO. L.P. CONFIGURATION. GOODMAN MFG. CO. L.P. Y/Y2 2ND STAGE HEATER NOTES: YLO/Y1 1ST STAGE HEATER 1.) OT2 CLOSED AND W2 DEMAND ENABLES...
  • Page 23 lead or jumper is connected between Test and YCON, the red A test lead or jumper wire can be added from the test terminal “+” LED will illuminate. The corresponding response from the to any terminal on the B13682-74 or B13682-71 variable speed CKTS control will be an illuminated “LOW”...
  • Page 24 That’s why we know . . . There’s No Better Quality. Visit our websites at www.goodmanmfg.com or www.amana-hac.com for information on: • Products • Warranties • Customer Services • Parts • Contractor Programs and Training • Financing Options © 2004-2009 Goodman Manufacturing Company, L.P.