Mitsubishi A8GT-50KBF User Manual page 18

External i/o interface module
Hide thumbs Also See for A8GT-50KBF:
Table of Contents

Advertisement

(b) Parts list
Number
1) 2)
Connector (with cover)
1)
Connector
2)
Connector cover
3)
Pair shielded cable
4)
FG wire
(c) Assembly
1) 2)
POINT
" The cable fabricated should be within 3m in length .
" Connect the FG cable to the nearest ground
" The grounding wire (green wire, approx. 1m) coming out of the connector of
the user-fabricated connection cable must be connected to the control box
or the like.
" Grounding should be independent where possible.
" Use class D grounding (class 3 grounding) method (grounding resistance is
100 Ω max.).
" The grounding point should be as near as possible to the external I/O
module to minimize the grounding cable length.
" Adjust the grounding cable length according to the grounding position and
install a terminal or the like for grounding.
" When grounding, always connect the FG cable for connection with the GOT
's power supply terminal block and the FG wire of the user-fabricated
connection cable separately.
Name
A6CON1
FCN-361JO40-AU
FCN-360CO40-B
UL 2464 AWG26 or equivalent
UL 1015 AWG14 or equivalent
4)
Type
3)
12
Maker
Mitsubishi
Electric
Fujitsu

1) 2)