Gree R410A Service Manual page 163

Super free match series t1/r410a/50hz
Hide thumbs Also See for R410A:
Table of Contents

Advertisement

6.Solder the
pipeline with the
suction and
discharge ports of
the compressor
7.Reconnect the
power cords
8.Put back the electric heating belt and the discharge temperature sensor etc.
9.Check and
screw back the
plates
 
Super Free Match
Service Manual
Solder the connecting
pipe to make them
connected
Note:
never let the
flame contact any other
component.
a)
Tighten the fixing
screw of the power
cord.
b)
Connect the power
cord.
Note: mark the color
of the power cord and
corresponding terminal.
a)
Check if the pipe is
well connected.
b)
Check if the parts and
wire well connected.
c)
If there is no
problem, fix the
cover.
159
MAINTENANCE
N

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents