York 018-060 Technical Manual page 18

Split-system air conditioners 10 seer 1.5 thru 5 nominal tons, 1 ph/3 thru 7.5 nominal tons, 3 ph
Table of Contents

Advertisement

036-21122-002 Rev. B (0103)
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO.
INDOOR COIL MODEL NO.
CONDENSER
ENTERING AIR
TEMPERATURE
75
85
95
105
115
125
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.
Air Handler
Coil
N1AHD2046
G2FD060(S,H)24
F2FP060
G1FA060S21,24
G1NA060S24T
G1UA060S21,24
18
HABA-(T,W)060S
G2FD060S24A
ID CFM
1450
ID DB (°F)
85
80
ID WB (°F)
72
67
T.C.
61.2
58.5
S.C.
37.6
37.4
K.W
4.66
4.57
T.C.
60.6
58.0
S.C.
37.6
37.3
K.W
5.26
5.13
T.C.
60.0
57.4
S.C.
37.5
37.1
K.W
5.86
5.70
T.C.
58.1
54.6
S.C.
36.9
36.0
K.W
6.54
6.39
T.C.
56.2
51.8
S.C.
36.2
34.9
K.W
7.23
7.07
T.C.
54.3
49.0
S.C.
35.6
33.8
K.W
7.92
7.76
T.C.
S.C.
KW
1.00
1.00
1.00
1.00
1.00
1.05
1.00
1.00
1.00
0.98
0.98
1.01
1.00
1.00
1.00
1700
70
85
80
57
72
67
56.3
61.8
59.1
37.1
40.1
39.9
4.51
4.67
4.58
55.0
61.2
58.6
36.5
40.2
39.9
5.08
5.27
5.14
53.7
60.7
58.5
35.9
40.3
39.8
5.65
5.87
5.71
50.0
58.9
55.7
34.4
39.8
39.0
6.29
6.56
6.42
46.3
57.1
53.2
32.9
39.3
38.1
6.92
7.25
7.12
42.6
55.2
50.6
31.4
38.7
37.2
7.55
7.94
7.83
1950
70
85
80
57
72
67
56.9
62.3
59.6
39.5
42.5
42.3
4.53
4.68
4.58
55.8
61.9
59.3
39.1
42.8
42.5
5.10
5.28
5.15
54.8
61.4
59.0
38.8
43.1
42.6
5.67
5.88
5.72
51.3
59.7
56.8
37.3
42.7
41.9
6.30
6.57
6.45
47.9
57.9
54.5
35.9
42.3
41.2
6.94
7.26
7.17
44.5
56.2
52.3
34.4
41.9
40.5
7.58
7.96
7.90
Unitary Products Group
70
57
57.5
41.8
4.55
56.7
41.7
5.11
55.8
41.6
5.68
52.7
40.2
6.32
49.5
38.8
6.97
46.4
37.4
7.62