Cooling Capacity - Upflow, Downflow, & Horizontal Furnaces And Coils - York H1RA018S06 Technical Manual

Split-system air conditioners 10 seer
Hide thumbs Also See for H1RA018S06:
Table of Contents

Advertisement

036-21121-002 Rev. B (0103)
COOLING CAPACITY - Upflow, Downflow, & Horizontal Furnaces and Coils
FURNACE**
UNIT MODEL
CFM RANGE
(MIN.-MAX.)
575
H1RA018S06
725
700
H1RA024S06
900
875
H2RA030S06
1125
1050
H2RA036S06
1350
For Notes See Page 5.
6
COIL
MODEL
W
14,17
G1FA024S14,17
14
G1FA030S14
-
G1HD024
17
G1NA024S17G
14,17
G1UA024S14,17
14
G1UA030S14
14,17
G2FD024(S,H)14,17
17
G2FD030(S,H)17
14
G2FD035(S,H)14
14,17
G1FA024S14,17
14
G1FA030S14
14
G1FA036S14
17,21
G1FA036S17,21
-
G1HD024
-
G1HD036
17
G1NA030S17H
21
G1NA030S21B
14,17
G1UA024S14,17
14
G1UA030S14
14
G1UA036S14
17,21
G1UA036S17,21
14,17
G2FD024(S,H)14,17
17
G2FD030(S,H)17
14
G2FD035(S,H)14
17
G2FD036(S,H)17
14
G1FA030S14
14
G1FA036S14
17,21
G1FA036S17,21
-
G1HD036
17
G1NA030S17K
21
G1NA030S21M
14
G1UA036S14
17,21
G1UA036S17,21
17
G2FD030(S,H)17
14
G2FD035(S,H)14
21
G2FD036(S,H)21
14
G1FA036S14
17,21
G1FA036S17,21
17
G1FA048S17
21,24
G1FA048S21
-
G1HD036
-
G1HD048
17
G1NA036S17J
21
G1NA036S21C
14
G1UA036S14
17,21
G1UA036S17,21
17
G1UA048S17
21,24
G1UA048S21
14
G2FD035(S,H)14
17
G2FD036(S,H)17
21
G2FD036(S,H)21
21
G2FD042(S,H)21
17
G2FD046(S,H)17
COOLING
NET MBH
RATED
CFM
TOTAL
SENS.
650
18.0
13.3
650
19.0
14.1
655
18.5
13.7
650
18.0
12.5
650
18.0
13.3
650
19.0
14.1
650
19.0
14.1
650
19.4
14.4
650
19.4
14.4
850
23.8
17.6
800
24.4
18.1
800
24.0
18.1
850
25.0
18.5
820
23.2
17.2
800
24.4
18.1
800
23.6
17.5
800
23.6
17.5
850
23.8
17.6
800
24.4
18.1
800
24.0
18.5
850
25.0
18.5
800
24.4
18.5
850
25.0
18.5
850
25.0
18.9
850
25.6
18.9
1000
28.0
20.7
1000
29.2
20.3
1000
29.0
21.5
1000
29.6
21.9
1000
29.0
20.4
1050
29.0
20.4
1000
29.2
20.3
1000
29.0
21.5
1000
29.0
21.5
1000
29.0
21.5
1000
30.0
22.2
1200
33.6
24.9
1200
33.6
24.9
1200
35.0
25.9
1200
36.0
26.6
1200
34.4
25.5
1165
34.8
25.8
1200
34.4
25.5
1200
34.4
25.5
1200
33.6
24.9
1200
33.6
24.9
1200
35.0
25.9
1200
36.0
26.6
1200
33.4
24.7
1200
33.8
25.0
1200
33.8
25.0
1200
34.4
25.5
1200
34.4
25.5
SEER
1
SEER + TXV
W/O TXV
10.00
-
10.50
-
10.50
-
10.00
-
10.00
-
10.50
-
10.50
-
10.50
-
10.50
-
10.00
-
10.50
-
10.00
-
10.00
-
10.00
-
10.60
-
10.00
-
10.00
-
10.00
-
10.50
-
10.00
-
10.00
-
10.50
-
10.60
-
10.60
-
10.70
-
10.00
-
10.25
-
10.45
-
10.00
-
10.00
-
10.00
-
10.25
-
10.45
-
10.30
-
10.30
-
10.50
-
10.00
-
10.00
-
10.30
-
10.40
-
10.00
-
10.00
-
10.00
-
10.00
-
10.00
-
10.00
-
10.30
-
10.40
-
10.00
-
10.00
-
10.00
-
10.15
-
10.15
-
Unitary Products Group
EER
9.20
9.80
10.00
9.40
9.20
9.80
9.80
9.90
9.90
9.15
9.55
9.00
8.95
8.80
9.80
9.00
9.00
9.15
9.55
9.00
8.95
9.55
9.65
9.65
9.70
9.30
9.40
9.45
9.55
9.30
9.20
9.40
9.45
9.45
9.45
9.65
9.10
9.10
9.40
9.40
8.90
8.95
9.20
9.30
9.10
9.10
9.40
9.40
9.10
9.20
9.20
9.30
9.30