7.
Make sure the extension cord is properly wired and in good electrical condition.
Always replace a damaged extension cord or have it repaired by a qualified elec-
trician before using it.
8.
Protect the extension cords from sharp objects, excessive heat, and damp or wet
areas.
recoMMended MiniMuM wire gauge For eXtension cords*
naMeplate
aMperes
(at full load)
0 – 2.0
2. – 3.4
3.5 – 5.0
5. – 7.0
7. – 2.0
2. – 6.0
6. – 20.0
table a
Double Insulated
Canadian Standards Association
Underwriters Laboratories, Inc.
9.
All connections and conduits from the Generator to the load must only be in-
stalled by trained and licensed electricians, and in compliance with all relevant
local, state, and federal electrical codes and standards, and other regulations.
0.
The Generator must be earth-grounded in accordance with all relevant electrical
codes and standards before operation.
.
If an extension cord (not included) is used, make sure to use only UL listed cords
having the correct gauge and length.
2.
Do not attempt to connect or disconnect load connections while standing in wa-
ter, or on wet or soggy ground.
SKU 96898
For technical questions, please call 1-800-444-3353.
eXtension cord lengtH
25 Feet
50 Feet
8
8
8
8
8
8
8
6
8
4
4
2
2
0
* Based on limiting the line voltage drop to five volts at 150% of the rated amperes.
symbology
75 Feet
100 Feet
8
8
6
4
2
0
-
V~
Volts Alternating Current
a
Amperes
No Load Revolutions per Minute
n 0 xxxx/min.
(RPM)
(120/240 Volt)
150 Feet
8
6
6
4
4
2
2
2
0
-
-
-
-
-
Page 0