Biasi M96.24SM/B Service Manual page 34

Wall hung, fan flue, room sealed, high efficiency gas boiler
Hide thumbs Also See for M96.24SM/B:
Table of Contents

Advertisement

17
By---pass valve
17.1
Function
The By---pass valve A in Fig. 65 is located between the
c.h. water flow and return and its function is that of guar-
anteeing a minimum flow across the primary heat ex-
changer if the circulation across the c.h. system is com-
pletely closed.
The By---pass valve is fitted on the rear side of the div-
erter group.
Fig. 65
32
A
17.2
Removal
Warning: isolate the boiler from the mains
electricity supply before removing any
covering or component.
1
Remove all the case panels.
2
Empty the primary circuit of the boiler.
3
Remove the diverter group as described in the
section 9.4 of this manual.
Unscrew the connector B and remove the by---
4
pass valve C (Fig. 66).
B
C
Fig. 66
5
Reassemble the by---pass valve as illustrated in
Fig. 66 reversing the order of removal.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents