Stanley Cara Installation And Operating Instructions Manual
Stanley Cara Installation And Operating Instructions Manual

Stanley Cara Installation And Operating Instructions Manual

Non boiler insert stove

Advertisement

Cara Non Boiler
Insert Stove
This appliance is hot while in operation and retains its heat for a long period of time after use.
Children, aged or infirm persons should be supervised at all times and should not be allowed
to touch the hot working surfaces while in use or until the appliance has thoroughly cooled.
When using the stove in situations where children, aged and/or infirm persons are
present a fireguard must be used to prevent accidental contact with the stove. The fireguard
should be manufactured in accordance with BS 8423:2002.
INSTALLATION AND OPERATING INSTRUCTIONS

Advertisement

Table of Contents
loading

Summary of Contents for Stanley Cara

  • Page 1 Cara Non Boiler Insert Stove This appliance is hot while in operation and retains its heat for a long period of time after use. Children, aged or infirm persons should be supervised at all times and should not be allowed to touch the hot working surfaces while in use or until the appliance has thoroughly cooled.
  • Page 2: Table Of Contents

    TABLE OF CONTENTS PAGE NO. Insert Stove Installation & Operating Instructions ......General .
  • Page 3: Insert Stove Installation & Operating Instructions

    INSERT STOVE INSTALLATION & OPERATING INSTRUCTIONS NOTE: Please note that it is a legal requirement The installation must be completed in under England & Wales Building Regulations that accordance with current National the installation of the stove is either carried out European Standards and Local Codes.
  • Page 4: Chimney

    Fig.2B construction with no leaks or cracks, a clay flue liner has been used that can withstand up to 1000 C, the clay liner has a diameter no greater than 200mm. The chimney must be swept and examined for soundness and suitability before the appliance is installed.
  • Page 5: Not Fully Lined Chimney

    the spigot in place while the fixings are being 240mm - 320mm Fig.4 attached. Step 10 405mm - 455mm Complete the installation of the flexi flue at the top of the chimney in accordance with the manufacturers instructions. NOT FULLY LINED CHIMNEY (Using Closure Plate &...
  • Page 6 Fig.7 Step 4 Push the offset adaptor into position and make a seal using approved fire cement between the adap- tor and the clay liner. The seal should be tapered to allow any condensation that may occur in the chimney flow back into the flue. See Fig.7. Step 5 Mark the drill locations and drill the holes using a 5.5mm drill bit.
  • Page 7: Down Draughts

    4. Fixed Baffle Fit the individual components in the following order: The baffle fits to the roof of the stove using the two 1. Grate Support M6 round head screws. With the screws in place, lift 2. Grate the baffle into place with the main part of the baffle 3.
  • Page 8: Ventilation & Combustion Air Requirements

    Air vents direct to the outside of the building should Fig 10 Direction of wind be located so that any air current produced will not pass through normally occupied areas of the room. An air vent outside the building should not be locat- ed less than the dimensions specified within the Building Regulations and B.S.
  • Page 9: Extractor Fan

    Extractor Fan Fig.11 There must not be an extractor fan fitted in the same room as the stove as this can cause the stove to emit smoke and fumes into the room. COMMISSIONING & HANDOVER On completion of the installation allow a suitable period of time for any fire cement and mortar to dry out, when a small fire may be lit and checked to ensure the smoke and fumes are taken from the...
  • Page 10: Floor Protection

    Building Regulations must extend to the front of the appliance. CO ALARM Waterford Stanley strongly recommend the fitting of a CO Alarm in the same room as the appliance, this is a compulsory requirement under UK Building Regulations.
  • Page 11: Primary Air Control Spin Valve

    AIR CONTROLS When burning wood the primary air control should be adjusted to a maximum of one turn open after the The stove has two air controls the primary and sec- fire has established, when wood is very well sea- ondary.
  • Page 12: Slow Burning

    Fig.18 When burning wood the requirement to riddle the fire is much less. Do not riddle the fire with the spin- wheel open but fully open the secondary air control instead. Remember to reset the controls after refuelling. Fig.17 MAINTENANCE GRATE REMOVAL &...
  • Page 13: Chimney Cleaning

    It is also important to clean the appliance flue-ways, Fig.20 flue-pipe and chimney prior to lighting up after a prolonged shut-down period. REMEMBER COAL GASES ARE TOXIC WARNING There must not be an extractor fan fitted in the same room as the stove as this can cause the stove to emit fumes into the room.
  • Page 14: Lighting

    Use only replacement parts recommended by Waterford Your Installer should have fitted a CO Alarm in the Stanley. Using unauthorised parts will invalidate same room as the appliance. your guarantee and may cause damage or injury.
  • Page 15: Fire Safety

    FIRE SAFETY SUMMER SHUTDOWN To provide reasonable fire safety the following For summer shutdown of the stove, ensure all ashes should be given serious consideration: have been cleaned from the ash compartment and that the air control is open, to avoid condensation in 1.
  • Page 16: Exploded View

    CARA INSERT STOVE EXPLODED VIEW SPIN VALVE - B00032AZZ 17. MIN SPRING HANDLE - L00539AXX FIRE DOOR - B00587AZZ 18. FLUE GASKET - P00102AXX FRONT - B00588AZZ 19. 5” FLUE - Q00752AXX WINDOW CLIP - F00896BXX 20. TOP BAFFLE -...

Table of Contents