Testing Your Calibration - AMX Modero CV7 Operation/Reference Manual

7" modero touch panel
Hide thumbs Also See for Modero CV7:
Table of Contents

Advertisement

Panel Calibration
FIG. 47
Touch Panel Calibration Screens
3. After the "Calibration Successful.." message appears, press anywhere on the screen to continue and
return to the Setup page.
If the calibration was improperly set and you cannot return to the Calibration
page (through the panel's firmware); you can then access this firmware page via
G4 WebControl where you can navigate to the Protected Setup page and press the
Calibrate button through your VNC window.
This action causes the panel to go to the Calibration page seen above, where you
can physically recalibrate the actual touch panel again using the above procedures.

Testing your Calibration

1. Press and hold down the on-screen Calibration button for 6 seconds to enter the Calibration Test
page (FIG. 48).
FIG. 48
Calibration Test page
2. Press anywhere on this page to confirm the on-screen crosshairs match your touch points.
3. If the crosshairs do not appear directly below your LCD touch points, press the Back button and
recalibrate the panel using the above steps.
4. Exit this Calibration Test page by pressing the Back button to return to the Protected Setup page.
48
The request to touch the crosshairs
is the first on-screen message
Calibration successful is the second
on-screen message that appears
after the calibration process is
completed
On-screen crosshairs used for
calibration of the touch device
On-screen crosshairs is used to
verify a proper calibration of the
panel
7" Modero Touch Panels