Carrier 40UV Installation, Start-Up And Service Instructions Manual page 16

Unit ventilators with product integrated control (pic)
Table of Contents

Advertisement

UNIT
HP
40UV,UH100
1
/
3
(at 1000 Cfm)
LEGEND
DX
— Direct Expansion
FLA
— Full Load Amps
LAT
— Leaving-Air Temperature at 70 F Entering-Air
Temperature
MCA
— Unit Minimum Circuit Ampacity
MOCP — Maximum Overcurrent Protection (Maximum Fuse Size
or Circuit Breaker Amps)
PSC
— Permanent Split Capacitor
Table 3 — Electric Heater Data for Units with ECM (cont)
NUMBER
NOMINAL
OF
V/Ph/Hz
ELEMENTS
3
4
208/1/60
5
6
3
4
240/1/60
5
6
3
4
277/1/60
5
6
3
4
208/3/60
5
6
3
4
240/3/60
5
6
3
4
460/3/60
5
6
LAT
FLA
(F)
31.5
89
41.1
95
50.8
102
60.4
108
35.9
96
47.1
104
58.2
112
69.3
121
31.2
96
40.8
104
50.4
112
60.1
121
19.3
89
28.9
95
36.0
102
36.0
108
21.9
96
33.0
104
41.1
112
41.1
121
10.6
96
16.2
104
20.3
112
20.3
121
NOTES:
1. LAT (Leaving Air Temperature) (F) is measured at nominal cfm.
2. Water and DX coil used on electric heat units have left-hand
coil connections.
3. Electric heat is available in the reheat position only and connec-
tions are on the right side.
4. Face and bypass units are available with 3 heating elements
only.
16
TOTAL
MCA
MOCP
CAPACITY
39.4
40
51.4
60
63.4
70
75.5
80
44.9
45
58.8
60
72.7
80
86.6
90
39.0
40
51.0
60
63.1
70
75.1
80
24.1
25
36.2
40
45.0
50
45.0
50
27.3
30
41.2
45
51.4
60
51.4
60
13.3
15
20.2
25
25.3
30
25.3
30
(kW)
6.0
8.0
10.0
11.9
8.0
10.7
13.3
16.0
8.0
10.7
13.3
16.0
6.0
8.0
10.0
11.9
8.0
10.7
13.3
16.0
8.0
10.7
13.3
16.0