Carrier 40UV Installation, Start-Up And Service Instructions Manual page 11

Unit ventilators with product integrated control (pic)
Table of Contents

Advertisement

UNIT
HP
40UV,UH100
1
/
5
(at 1000 Cfm)
LEGEND
DX
— Direct Expansion
FLA
— Full Load Amps
LAT
— Leaving-Air Temperature at 70 F Entering-Air
Temperature
MCA
— Unit Minimum Circuit Ampacity
MOCP — Maximum Overcurrent Protection (Maximum Fuse Size
or Circuit Breaker Amps)
PSC
— Permanent Split Capacitor
Table 2 — Electric Heater Data for Units with PSC Motor (cont)
NUMBER
NOMINAL
OF
V/Ph/Hz
ELEMENTS
3
4
208/1/60
5
6
3
4
240/1/60
5
6
3
4
277/1/60
5
6
3
4
208/3/60
5
6
3
4
240/3/60
5
6
3
4
460/3/60
5
6
LAT
FLA
(F)
30.9
89
40.5
95
50.2
102
59.8
108
35.3
96
46.5
104
57.6
112
68.7
121
30.5
96
40.1
104
49.7
112
59.4
121
18.7
89
28.3
95
35.4
102
35.4
108
21.3
96
32.4
104
40.5
112
40.5
121
10.6
96
16.1
104
20.2
112
20.2
121
NOTES:
1. LAT (Leaving Air Temperature) (F) is measured at nominal cfm.
2. Water and DX coil used on electric heat units have left-hand
coil connections.
3. Electric heat is available in the reheat position only and connec-
tions are on the right side.
4. Face and bypass units are available with 3 heating elements
only.
11
MCA
MOCP
CAPACITY
38.6
40
50.7
60
62.7
70
74.7
80
44.2
45
58.1
60
72.0
80
85.8
90
38.1
40
50.1
60
62.2
70
74.2
80
23.4
25
35.4
40
44.3
45
44.3
45
26.6
30
40.5
45
50.7
60
50.7
60
13.2
15
20.1
25
25.2
30
25.2
30
TOTAL
(kW)
6.0
8.0
10.0
11.9
8.0
10.7
13.3
16.0
8.0
10.7
13.3
16.0
6.0
8.0
10.0
11.9
8.0
10.7
13.3
16.0
8.0
10.7
13.3
16.0