Zoning Disable; Zone Offsets; Zone Airflow Limits - Bryant Evolution Connex SYSTXBBECW01 Installation Instructions Manual

Controller
Hide thumbs Also See for Evolution Connex SYSTXBBECW01:
Table of Contents

Advertisement

6.3.6.1.

Zoning Disable

This option allows the installer to enable or disable zoning. After the selection is
made, touch SAVE.
Disable Zoning: Yes or No
S
Default = No
d
6.3.6.2.

Zone Offsets

This option allows actual temperature offset for each zone, allowing calibration (or
deliberate miscalibration) of each sensor. Use the Left (<) or Right (>) buttons to
change the zone. After the selection is made, touch SAVE.
Temperature Offset: Adjustable between - - 5 to 5_F (- - 3 to 3_C)
S
Default = 0_F
d
6.3.6.3.

Zone Airflow Limits

Since a bypass damper is prohibited in this system, this setting is used to select the
maximum allowable noise/airflow relationship into each zone based on air noise
and comfort requirements. LOW means 100% of maximum assessed airflow;
MED- - LOW means 138% of maximum assessed airflow; MEDIUM means 176%
of maximum assessed airflow; MED- - HIGH means 214% of maximum assessed
36
A12191