For hydronic heat applications, this option allows the installer to set the lockout
temperatures below the which only the hydronic coil will operate, and the lockout
temperature above which the hydronic coil will not operate. After the selections are
made, touch SAVE.
HP Lockout: Adjustable from 5 to 55_F (- - 15 to 13_C) or None
S
Default = None
d
Furnace, Electric Heat or Hydronic Lockout: Adjustable from 5 to 55_F
S
(- - 15 to 13_C) or None
Default = None
d
Defrost with Furnace, Electric Heat or Hydronic: Yes or No
S
Default = Yes
d
6.3.6.
Zoning (if applicable)