Close to or in direct airflow from supply registers.
S
In areas with poor air circulation, such as behind a door or in an alcove.
S
4.3.2.

Remote Room Sensors

A Remote Room Sensor can be used with the Evolution Connex Control to take the
place of the control's internal temperature sensor. This allows the Evolution Connex
Control to be mounted in areas with less than optimal airflow (such as near an
exterior door, window or in a closet). The remote sensor can be wired to the
terminal block connectors labeled S1 and S2 at the control's backplate, or the ZS1
and ZS1C connection at the Damper Control Module. In either case, the Evolution
Connex Control will automatically detect the Remote Room Sensor and ignore its
internal temperature sensor.
4.3.2.1.

Remote Room Sensor Averaging

Typically, one remote sensor is used but, multiple sensors may be used and
averaged in some applications. Averaging requires a special series- - parallel wiring
method with a specific number of sensors. See figure below. It is also important to
note the humidity sensor cannot be remotely located, so do not locate the Evolution
Control in an area where humidity sensing may not be accurate.
Damper Control
Module
ZS_
Sensor 1
Sensor 2
Sensor 3
Sensor 4
6
Damper Control
Module
ZS_C
A03233