Set Temperature Rise; Set Thermostat Heat Anticipator - Carrier 58MVP Installation, Start-Up, And Operating Instructions Manual

170 series 4-way multipoise direct-vent variable-capacity condensing for sizes 040—120
Table of Contents

Advertisement

m. Move setup switch SW1-2 to OFF position and jumper R
and W/W1 and W2 thermostat connections. (See Fig. 32.)
This keeps furnace locked in high-heat operation. Repeat
items i through l for high-heat operation.
EXAMPLE: (High-heat operation at 0—2000 ft altitude)
Furnace input from rating plate is 100,000 Btuh
Btu heating input = Btu/cu ft X cu ft/hr
Heating value of gas = 975 Btu/cu ft
Time for 1 revolution of 2-cu ft dial = 70 sec
Gas rate = 103 cu ft/hr (from Table 13)
Btu heating input = 103 X 975 = 100,425 Btuh In this
example, the orifice size and manifold pressure adjustment
is within ±2 percent of the furnace input rate.
NOTE: Measured gas inputs (high heat and low heat) must be
within ±2 percent of that stated on furnace rating plate when
installed at sea level or derated per that stated above when installed
at higher altitudes.
n. Remove jumper across R, W/W1, and W2 thermostat
connections to terminate call for heat.
Table 13—Gas Rate Cu Ft/Hr
SIZE OF TEST DIAL
SECONDS
FOR 1
1
2
REVOLUTION
cu ft
cu ft
cu ft
10
360
720
1800
11
327
655
1636
12
300
600
1500
13
277
555
1385
14
257
514
1286
15
240
480
1200
16
225
450
1125
17
212
424
1059
18
200
400
1000
19
189
379
947
20
180
360
900
21
171
343
857
22
164
327
818
23
157
313
783
24
150
300
750
25
144
288
720
26
138
277
692
27
133
267
667
28
129
257
643
29
124
248
621
30
120
240
600
31
116
232
581
32
113
225
563
33
109
218
545
34
106
212
529
35
103
206
514
36
100
200
500
37
97
195
486
38
95
189
474
39
92
185
462
40
90
180
450
41
88
176
439
42
86
172
429
43
84
167
419
44
82
164
409
45
80
160
400
46
78
157
391
47
76
153
383
48
75
150
375
49
73
147
367
SIZE OF TEST DIAL
SECONDS
FOR 1
5
1
2
REVOLUTION
cu ft
cu ft
50
72
144
51
71
141
52
69
138
53
68
136
54
67
133
55
65
131
56
64
129
57
63
126
58
62
124
59
61
122
60
60
120
62
58
116
64
56
112
66
54
109
68
53
106
70
51
103
72
50
100
74
48
97
76
47
95
78
46
92
80
45
90
82
44
88
84
43
86
86
42
84
88
41
82
90
40
80
92
39
78
94
38
76
96
38
75
98
37
74
100
36
72
102
35
71
104
35
69
106
34
68
108
33
67
110
33
65
112
32
64
116
31
62
120
30
60

SET TEMPERATURE RISE

Temperature rise must be within limits specified on unit
rating plate. Operation is within a few degrees of midpoint of
rise range when setup switch SW1-4 is OFF. Failure to follow
this caution may result in overheating the heat exchangers or
condensing flue gas in heat exchanger areas not designed for
condensate.
Furnace must operate within ranges of temperature rise specified
on the furnace rating plate. Determine air temperature rise as
follows:
1. Place thermometers in return and supply ducts as near furnace
as possible. Be sure thermometers do not see heat exchanger
so that radiant heat does not affect readings. This practice is
particularly important with straight-run ducts.
2. When thermometer readings stabilize, subtract return-air tem-
perature from supply-air temperature to determine air tem-
perature rise.
NOTE: Temperature rise can be determined for low-heat opera-
tion by placing setup switch SW1-2 on furnace control in ON
position. For high-heat operation, place setup switch SW1-2 in
OFF position and jumper R-W2 on furnace control. DO NOT
forget to return setup switch to OFF position and remove R-W2
jumper upon completion of testing. (See Fig. 32 for switch and
terminal location.)
3. This furnace is capable of automatically providing proper
airflow to maintain the temperature rise within the range
specified on furnace rating plate. If temperature rise is outside
this range, proceed as follows:
a. Check gas input for low- and high-heat operation.
5
cu ft
b. Check derate for altitude if applicable.
360
c. Check all return and supply ducts for excessive restrictions
355
346
causing static pressure greater than 0.5-in. wc.
340
d. Ensure Low Heat Rise Adjust switch SW1-3 on furnace
333
control is in ON position when a bypass humidifier is used.
327
321
(See Fig. 32 for switch location.)
316
310
e. Check Troubleshooting Guide for Variable-Speed 2-Stage
305
Electronic Condensing Furnaces Series 170 and later.
300

SET THERMOSTAT HEAT ANTICIPATOR

290
281
When using a non-electronic thermostat, the thermostat heat
273
anticipator must be set to match the amp draw of components in
265
257
the R-W/W1 circuit. Accurate amp draw measurements can be
250
obtained only at the thermostat subbase terminals R and W.
243
237
The thermostat and anticipator should NOT be in the circuit while
231
measuring current. If thermostat has no subbase, the thermostat
225
must be disconnected from R and W/W1 wires during current
220
measurement.
214
209
Fig. 65 illustrates an easy method of obtaining thermostat amp
205
draw measurements. The amp reading should be taken after blower
200
196
motor has started and furnace is operating in low-heat.
192
1. To operate furnace in low-heat, turn setup switch SW1-2 to
188
184
ON position (See Fig. 32) and connect ammeter leads across
180
thermostat subbase R-W.
178
2. See thermostat manufacturer's instructions for adjusting the
173
170
heat anticipator and for varying heating cycle length.
167
NOTE: When using an electronic thermostat, set cycle rate for 3
164
cycles per hr.
161
155
3. Return setup switch SW1-2 to OFF position and replace
150
thermostat on subbase.
48

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents