Installation Instructions Installation Location Selection; Selecting Installation Place; Outdoor Unit - Heat Controller A-VFH24TA-1 Installation, Operation & Maintenance Manual

Inverterflex series outdoor ductless mini-split heat pumps
Table of Contents

Advertisement

VFH InverterFlex
- Outdoor Ductless Mini-Split
®

Selecting installation place

Choose a location that places the outdoor unit as
close to the indoor unit as possible. The maximum
unit separation and vertical lift (distance compressor is
above the evaporator) must be taken into account. Do
not exceed allowable refrigerant line lengths.
Fig. 1
Min. 1.5ft.
(500mm)
Min. 6.5ft. (2000mm)
(Air outlet side)
Fig. 2
Incorrect

Outdoor unit

• Unit must be installed in a location that does not
obstruct the airflow and ensures clearance are
maintained (Fig. 1)
• If installation location allows the unit to be exposed
to strong winds (such as coastal applications),
ensure that the unit has a wind barrier. This will
assist with preventing strong gusts of wind from
entering the unit's cabinet and interfering with the
fan operation. (Fig. 2 and Fig. 3)
Min. 3.5ft.
Min. 1.5ft.
(1000mm)
(500mm)
(Air inlet side)
Fig. 3
Correct
Correct
6
Heat Controller
Min. 1.5ft. (500mm)
Space to the wall
Incorrect