Heat Controller A-VFH24TA-1 Installation, Operation & Maintenance Manual page 11

Inverterflex series outdoor ductless mini-split heat pumps
Table of Contents

Advertisement

Heat Controller
Refrigerant Line Set Installation
VFH InverterFlex System Line Set Requirements
For systems with only one indoor unit, the maximum line set length (Lx) is:
Outdoor Model
Maximum Length (Lx)
A-VFH18/24/30
32.8ft (10m)
A-VFH36/42
82ft (25m)
For systems with more than one indoor unit, the entire system must pass BOTH requirements below.
Maximum Length Requirement based on Indoor Unit Capacity:
Indoor Model
Maximum Length
B-VFH09
49.2ft (15m)
B-VFH12
65.6ft (20m)
B-VFH18/24
82ft (25m)
Total Allowable Length based on Outdoor Unit Capacity:
Outdoor Model
Zoning Based on Actual Number of Indoor Units Installed
Dual Zone
(L1+L2)
A-VFH18/24/30 98.4ft
(30m)
A-VFH36/42
104.9ft
(32m)
Single Zone Example:
An Outdoor A-VFH18 is installed with (1) B-VFH09 indoor unit. The line set must not exceed 32.8ft (10m) and the indoor
unit must not be more that 24.6 ft(7.5m) higher than the outdoor unit.
Multi-Zone Example:
Allowable Length and Height of Line Set
H1
H2
Max. Elevation Between Outdoor & Indoor Unit (H1)
24.6ft (7.5m)
49.2ft (15m)
Tri-Zone
Quad Zone
(L1+L2+L3)
(L1+L2+L3+L4)
172.25ft (52.5m)
229.6ft (70m)
157.5ft (48m)
209.9ft (64m)
VFH InverterFlex
Lx
(See Note 2)
Penta Zone
(L1+L2+L3+L4+L5)
N/A
262.5ft (80m)
11
- Outdoor Ductless Mini-Split
®
L
= Length of line set
x
from farthest indoor unit
Max.
Max. Elevation
Elevation
Difference
Between
Between each
Indoor &
Indoor Unit
Outdoor (H1)
(H2)
24.6 ft (7.5m)
24.6 ft (7.5m)
49.2 ft(15m)