FIREPLACE
INSTALLATION
Continued
To Gas Supply
(Natural)
To External
Regulator
(Propane/LP)
Flexible Gas Line
Do NOT Kink
Control Valve
Figure 52 - Connecting Flexible Gas Line
to Millivolt Valve
CHECKING GAS CONNECTIONS
WARNING: Test all gas piping
and connections, internal and
external to unit, for leaks after
installing or servicing. Correct
all leaks at once.
WARNING: Never use an
open flame to check for a leak.
Apply noncorrosive leak detec-
tion fluid to all joints. Bubbles
forming show a leak. Correct all
leaks at once.
pRESSURE TESTING GAS SUppLY
pIpING SYSTEM
Test Pressures In Excess Of 1/2 PSIG
(3.5 kPa)
1. Disconnect fireplace and its individual
equipment shutoff valve from gas supply
piping system. Pressures in excess of 1/2
psig (3.5 kPa) will damage fireplace gas
regulator.
2. Cap off open end of gas pipe where equip-
ment shutoff valve was connected.
3. Pressurize supply piping system by either
opening propane/LP supply tank valve for
propane/LP gas fireplace or opening main gas
valve located on or near gas meter for natural
gas fireplace or using compressed air.
4. Check all joints of gas supply piping sys-
tem. Apply noncorrosive leak detection
fluid to all joints. Bubbles forming show a
leak. Retighten all fittings.
116035-01J
Equipment
Shutoff Valve

www.desatech.com

5. If leaks still exist, turn off gas supply and
call a qualified service person.
6. Reconnect fireplace and equipment
shutoff valve to gas supply. Check recon-
nected fittings for leaks.
Test Pressures Equal To or Less Than
1/2 PSIG (3.5 kPa)
1. Close equipment shutoff valve (see Fig-
ure 53).
2. Pressurize supply piping system by either
opening propane/LP supply tank valve for
propane/LP gas fireplace or opening main gas
valve located on or near gas meter for natural
gas fireplace or using compressed air.
3. Check all joints from propane/LP supply
tank or gas meter to equipment shutoff
valve (see Figure 54 or Figure 55). Ap-
ply noncorrosive leak detection fluid to
all joints. Bubbles forming show a leak.
Retighten all fittings
4. If leaks still exist, turn off gas supply and
call a qualified service person.
Equipment
Shutoff Valve
Figure 53 - Equipment Shutoff Valve
Equipment Shutoff Valve
Propane/LP
Supply Tank
Figure 54 - Checking Gas Joints for
Propane/LP Gas Fireplace
Equipment
Shutoff Valve
Gas
Meter
Figure 55 - Checking Gas Joints for
Natural Gas Fireplace
Open
Closed
Gas Valve
Gas Valve
9