Toshiba RAV-SP1104AT8-E Service Manual page 73

Split-type outdoor unit
Hide thumbs Also See for RAV-SP1104AT8-E:
Table of Contents

Advertisement

Check
Outdoor
code
LED display
[H03]
<Display 1> <Display 2>
¡
¡
l
¡
l
l
<Display 1> <Display 2>
¡
¡
l
¡
¡
¡
[H04]
<Display 1> <Display 2>
¡
¡
l
¡
l
l
[L10]
<Display 1> <Display 2>
¡
¡
l
¡
¡
l
(Item without special mention Indicates part of outdoor unit.)
[Current detection circuit error]
¡
l
l
Check outdoor P.C. board (MCC-1596).
l
¥
¥
[Power supply error (Vdc)] o Refer to [P05] column.
¡
l
l
¥
l
¥
[Case thermostat operation]
¡
l
Are CN609 connection
l
and case thermostat normal?
¥
l
l
Is cooling/heating operation available
when short-circuiting case thermostat?
Is there no gas leak?
Is it not refrigerant shortage?
Is valve fully opened?
Is PMV normal?
[Unset model type] : Only when service P.C. board is used
¡
l
¥
Cut jumper line according
to the explanation sheet packaged
l
with the service P.C. board.
¥
l
Check and troubleshooting
Defect → Replace
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
– 73 –
Correct connector.
Case thermostat error → Replace
Check outdoor P .C. board (MCC-1599).
Defect → Replace
Repair defectives position.
Recharge refrigerant.
Open valve fully.
Correct defective position.
Replace defective part.
Check crushed or broken pipe.
Defect → Correct and Replace