Check
Outdoor
code
LED display
[F08]
<Display 1> <Display 2>
¡
¡
l
l
¡
¡
[F12]
<Display 1> <Display 2>
¡
¡
l
l
¡
¡
[F13]
<Display 1> <Display 2>
¡
¡
l
l
¡
¡
[F15]
<Display 1> <Display 2>
¡
¡
l
l
¡
¡
(Item without special mention Indicates part of outdoor unit.)
[Outside air temp. sensor (TO) error]
¡
l
Is CN602 connection normal?
¥
Is resistance value of TO sensor normal?
l
l
l
[Suction temp. sensor (TS) error]
¡
l
Is CN600 connection normal?
¥
Is resistance value of TS sensor normal?
¥
l
l
[Heat sink temp. sensor (TH) error]
¡
l
¥
Check outdoor P.C. board (MCC-1599).
¥
l
¥
[Miswiring of heat exchanger sensor (TE, TS)]
¡
l
Is mounting status of
¥
TE and TS sensors normal?
¥
¥
¥
Is CN600 connection normal?
Is resistance value of TS sensor normal?
Is CN601 connection normal?
Is resistance value of TE sensor normal?
Check and troubleshooting
YES
YES
Defect → Replace
YES
YES
YES
– 71 –
NO
Correct connector.
Sensor error → Replace
Check outdoor P.C. board (MCC-1599).
Defect → Replace
NO
Correct connector.
Sensor error → Replace
Check outdoor P.C. board (MCC-1599).
Defect → Replace
NO
Correct sensor mounting.
NO
Correct connector.
Sensor error → Replace
NO
Correct connector.
Sensor error → Replace
Check outdoor P.C. board (MCC-1599).
Defect → Replace