8.2.3 APPLIANCE VENT CONNECTION

Install the inner fl ex pipe to the appliance. Secure with 3 screws
A.
and fl at washers. Seal the joint and screw holes using the high
temperature sealant W573-0007 (not supplied).
Install the outer fl ex pipe to the appliance. Attach and seal
B.
the joints using the high temperature sealant W573-0002 (not
supplied).
8.3

GAS INSTALLATION

RISK OF FIRE, EXPLOSION OR ASPHYXIATION. ENSURE THERE ARE NO IGNITION SOURCES SUCH
SUPPORT GAS CONTROL WHEN ATTACHING GAS SUPPLY PIPE TO PREVENT DAMAGING GAS LINE.
ALWAYS LIGHT THE PILOT WHETHER FOR THE FIRST TIME OR IF THE GAS SUPPLY HAS RUN OUT
WITH THE GLASS DOOR OPENED OR REMOVED. PURGING OF THE GAS SUPPLY LINE SHOULD BE
PERFORMED BY A QUALIFIED SERVICE TECHNICIAN. ASSURE THAT A CONTINUOUS GAS FLOW IS AT
THE BURNER BEFORE CLOSING THE DOOR. ENSURE ADEQUATE VENTILATION. FOR GAS AND
ALL GAS CONNECTIONS MUST BE CONTAINED WITHIN THE APPLIANCE WHEN COMPLETE.
HIGH PRESSURE WILL DAMAGE VALVE. DISCONNECT GAS SUPPLY PIPING BEFORE TESTING GAS
Installation and servicing to be done by a qualifi ed installer. Do not use open fl ame.
Move the appliance into position and secure.
7.3.1
If equipped with a fl ex connector the appliance is designed to accept a 1/2" gas supply. Without the
7.3.2
connector it is designed to accept a 3/8" gas supply. The appliance is equipped with a manual shut off
valve to turn off the gas supply to the appliance.
Connect the gas supply in accordance to local codes. In the absence of local codes, install to the
7.3.3
current CAN/CSA-B149.1 Installation Code in Canada or to the current National Fuel Gas Code, ANSI
Z223.1 / NFPA 54 in the United States.
When fl exing any gas line, support the gas valve so that the lines are not bent or kinked.
7.3.4
The gas line fl ex-connector should provide suffi cient movement to permit shifting the burner assembly
7.3.5
on it's side.
Check for gas leaks by brushing on a soap and water solution.
7.3.6
W415-0811 / A / 04.28.10
AS SPARKS OR OPEN FLAMES.
ELECTRICAL LOCATIONS, SEE "DIMENSION" SECTION.
LINE AT TEST PRESSURES ABOVE 1/2 PSIG.
VALVE SETTINGS HAVE BEEN FACTORY SET, DO NOT CHANGE.
WARNING
!
#8 X 1/2"
SELF
DRILLING
SCREWS
2" OVERLAP
HIGH TEMPERATURE
SEALANT
28.2
30.1A