Hitachi WJ200 Series Quick Reference Manual page 65

Wj200 series inverter single-phase input 200v class three-phase input 200v class three-phase input 400v class
Hide thumbs Also See for WJ200 Series:
Table of Contents

Advertisement

CALL NOW 800-985-6929
Func.
Code
STOP key enable
B087
Restart mode after FRS
B088
Automatic carrier frequency
b089
reduction
Dynamic braking usage ratio
b090
Stop mode selection
B091
Cooling fan control
B092
Clear elapsed time of cooling
B093
fan
Initialization target data
b094
Dynamic braking control
b095
(BRD) selection
CALL NOW 800-985-6929
http://www.automatedpt.com
"b" Function
Name
Select whether the STOP key on the
keypad is enabled, three option
codes:
00...Enabled
01...Disabled always
02... Disabled for stop
Selects how the inverter resumes
operation when free-run stop (FRS)
is cancelled, three options:
00...Restart from 0Hz
01...Restart from frequency
detected from real speed of
motor (freq. matching)
02...Restart from frequency
detected from real speed of
motor (active freq. matching)
Three option codes:
00...Disabled
01...Enabled, depending on the
output current
02...Enabled, depending on the
heat-sink temperature
Selects the rate of use (in %) of the
regenerative braking resistor per
100 sec. intervals, range is 0.0 to
100%.
0%: Function disabled
>0%: Enabled, per value
Select how the inverter stops the
motor, two option codes:
00...DEC (decelerate to stop)
01...FRS (free-run to stop)
Selects when the fan is ON during
inverter operation, four options:
00...Fan is always ON
01...Fan is ON during run, OFF
during stop (5 minute delay
from ON to OFF)
02...Fan is temperature controlled
Two option codes:
00...Count
01...Clear
Select initialized parameters, four
option codes:
00...All parameters
01...All parameters except in/output
terminals and communication.
02...Only registered parameters in
Uxxx.
03...All parameters except
registered parameters in Uxxx
and b037.
Three option codes:
00...Disable
01...Enable during run only
02...Enable always
http://www.automatedpt.com
Description
63
Email: charles@automatedpt.com
Run
Defaults
Mode
Lnitial data
Units
Edit
00
00
01
-
0.0
%
00
01
-
00
-
00
-
01
-