Frequency Arrival Signals
The Frequency Arrival group of outputs helps coordinate external systems with the current
velocity profile of the inverter. As the name implies, output [FA1] turns ON when the output
frequency arrives at the standard set frequency (parameter F001). Output [FA2] relies on
programmable accel/ decel thresholds for increased flexibility. For example, you can have
an output turn ON at one frequency during acceleration, and have it turn OFF at a different
frequency during deceleration. All transitions have hysteresis to avoid output chatter if the
output frequency is near one of the thresholds.
Option
Terminal
Code
01
02
06
24
25
Valid for inputs:
Required
settings
Notes:
For most applications you will need to use
only one type of frequency arrival outputs (see
examples). However, it is possible assign both
output terminals to output functions [FA1] and
[FA2]
For each frequency arrival threshold, the
output anticipates the threshold (turns ON early)
by 1.5Hz
The output turns OFF as the output
frequency moves away from the threshold,
delayed by 0.5Hz
The example circuit for terminal [11] drives a
relay coil. Note the use of a diode to prevent the
negative going turn-off spike generated by the
coil from damaging the inverter's output
transistor
CALL NOW 800-985-6929
http://www.automatedpt.com
Function Name
Symbol
FA1
Frequency Arrival
Type 1 – Constant
Speed
FA2
Frequency Arrival
Type 2 – Over
frequency
FA3
Frequency Arrival
Type 3 – Set
frequency
FA4
Frequency Arrival
Type 4 – Over
frequency (2)
FA5
Frequency Arrival
Type 5 – Set
frequency (2)
11, 12, AL0 – AL2
C042, C043, C045, C046,
http://www.automatedpt.com
State
ON
when output to motor is at the constant frequency
OFF
when output to motor is OFF, or in any acceleration or
deceleration ramp
ON
when output to motor is at or above the set frequency
thresholds for, even if in acceleration or decel ramps
OFF
when output to motor is OFF, or during accel or decel
before the respective thresholds are crossed
ON
when output to motor is at the set frequency
OFF
when output to motor is OFF, or in any acceleration or
deceleration ramp
ON
when output to motor is at or above the set frequency
thresholds for, even if in acceleration or decel ramps
OFF
when output to motor is OFF, or during accel or decel
before the respective thresholds are crossed
ON
when output to motor is at the set frequency
OFF
when output to motor is OFF, or in any acceleration or
deceleration ramp
Example for terminal [11] (default output configuration
shown – see page 3-54):
Inverter output
terminal circuit
CM2
Example for terminal [AL0], [AL1], [AL2] (requires
output configuration – see
Inverter logic
circuit board
AL0
Power
supply
See I/O specs on
page 4-6
37
Email: charles@automatedpt.com
Description
FA1
11
RY
page
54):
FA1
AL1
AL2
Load